Product Description 

The FPT300.246-042-101 is a stand-alone power supply for three-phase mains systems, which 
provides a stabilized and galvanically separated PELV/ES1 output voltage at 4 outputs. The negative 
potential of the outputs is permanently connected to PE within the unit. 
The outputs fulfill the requirements for a limited power source according to NEC Class2. 
The housing is rated as IP54 according IEC60529 and provides protection against electrical, 
mechanical and fire hazards. 

Intended Use

 

This indoor use device is intended for commercial use, such as in industrial control, process control, 
monitoring, measurement or the like. 
Do not use this device in equipment, where malfunctioning may cause severe personal injury or 
threaten human life, without additional appropriate safety devices, that are suited for the end-
application. 
If used in a manner outside of its specification, the protection provided by the device may be impaired. 
WARNING: Risk of fire or electric shock. Do not interconnect output terminals. 

Installation Instructions 

Install the device with the terminals on the bottom of the device. Other mounting orientations require a 
reduction in output current. When installing watch out for the risk of injury from sharp edges and 
assure that when installed any sharp edges on the back cannot be accessed and cannot cause injury. 
The power supply is mounted on a bracket with 4 screws of size M4 ( UNC 8-32). For mounting the 
bracket use screws of equal or higher strength.  
The enclosure of the device provides a degree of ingress protection of IP54 when installed with all 
mating connectors firmly connected. The enclosure provides no protection against spilled liquids. 
The device is designed for pollution degree 2 areas in controlled environments. No condensation or 
icing is allowed. 
The device is designed as “Class of Protection I” equipment according to IEC 61140. Do not use 
without a proper PE (Protective Earth) connection. 
For TN,TT mains systems with earthed neutral and IT star mains systems with insulation monitoring 
the device is designed for overvoltage category III zones up to 2000m (6560ft) and for overvoltage 
category II zones up to 5000m (16400ft). For TN, TT, IT delta mains systems or IT star mains systems 
without insulation monitoring the device is intended for overvoltage category II zones up to 2000m 
(6560ft). 
The device is designed to be safe in case of a single phase loss and does not require an external 
protection. A disconnecting means shall be provided for the input of the device. 
The device is designed for convection cooling without a fan. Do not obstruct airflow. 
The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) a reduction in 
output current is required and the operation is limited according mains systems description above. 
Keep the following minimum installation clearances: 0mm on top, 30mm on the bottom, 15mm on the 
front and 0mm left and right side. 
The device is designed, tested and approved for branch circuits up to 20A (UL) and 32A (IEC) without 
additional protection device. If an external fuse is utilized, do not use circuit breakers smaller than 6A 
B- or C-Characteristic to avoid a nuisance tripping of the circuit breaker. 
Make sure that you only use plugs and cables rated for the device output current and the required 
temperature range. Follow all local and national codes for installation. 
The maximum permissible ambient air temperature is +70°C (+158°F). The operational temperature is 
the same as the ambient or ambient air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 5% and 95% relative humidity. 
Do not connect the negative potential of any output to PE. 
Cleaning only with a damp cloth.. 

Functional Description 

The output is electronically protected against no-load, overload and short circuit and can supply any 
kind of loads,

 

including inductive and capacitive loads. If capacitors with a capacitance >20mF are 

connected to one output, this output might switch off after turning the unit or the output on or 
connecting the load. 
Do not apply return voltages from the load to the output terminals higher than 35V. 
The green Status LED reports an output above 90% of the adjusted voltage of a running device and 
no output tripped due to overcurrent or overtemperature. 
The OUT-OK contact is closed when the Status LED is green and all outputs according settings. 
Contact ratings: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A for resistive loads. 
The device has an internal overtemperature protection. If the temperature is too high the unit shuts 
down and starts automatically again after cooling off. Each output will get the same state as before the 
shutdown. 
In case of an internal defect, a redundant circuit limits the maximum output voltage to 32.5V. The 
output shuts down and automatically attempts to restart. 
Do not parallel devices or outputs for higher output currents. 

LED bar and push-buttons: 

The LED bar normally displays the actual output power as percentage value. 100% equals an output 
power of 300W. LEDs up to and including 100% are green, the LEDs above 100% are orange. With 
the up and down button you can see the actual power per channel (orange LED indicates the currently 
selected channel). If you press the "Set Mode" button for 3 seconds all LEDs light up briefly and one 
LED stays on, showing the actual output voltage. With pressing the up or down button you can change 
the set voltage to the predefined values: 24V, 24.5V, 25V, 25.5V, 26V, 26.5V, 27V and 28V as printed 
aside the LEDS. The voltage is set immediately and the value stored until the next change. If no 
button is pressed for 15s unit returns to the normal state the LED bar will return to show the output 
power. 

Mating connectors: 

Use a Harting HANQ5/0 female plug to connect to the input voltage connector (X1).Pin assignment for 
the input connector (X1): Pin 1 for L1, Pin 2 for L2, Pin 3 for L3 and the Pin with the PE symbol for PE. 
Use a standard M12 A-coded 5 pin female plug to connect to the OUT-OK signal connector (X2).  
Pin assignment for the Output OK connector (X2): Pin 1 and Pin 4 for relay contact 
Use a standard M12 A-coded 5 pin male plug to connect to the output connectors (X2). Pin 1 for 
positive output pole, Pin 3 for the negative output pole and the Pin 2 and 4 not connected. 
 

 

Technical Data

 

All values are typical figures specified at 3x 400Vac 50Hz input voltage, 
symmetrical phase voltages, 24V, 300W output load, 25°C ambient 
temperature and after a 5 minutes run-in time unless otherwise noted. 

Output voltage 

DC 24V 

Nominal 

Adjustment range 

24 

– 28Vdc 

Factory setting 24.5V 

Output power 

Continuous: 

 

300W 

Below +55°C ambient 

 

150W 

At +70°C ambient 

 

Derate linearly b55°C and +70°C 

Number of outputs 

4  

NEC Class 2 

Current per output 

3.9 -3.4A 

 

Input voltage AC 

3AC 380 - 480V 

±15% 

Mains frequency 

50 

– 60Hz 

±6% 

Input current AC 

0.5 / 0.42A 

At 3x400 / 480Vac 

Power factor 

0.9 / 0.9 

At 3x400 / 480Vac 

Input inrush current 

1.5 / 1.5A peak 

At 3x400 / 480Vac, 
temp. independent 

Efficiency 

95.1 / 94.8% 

At 3x400 / 480Vac 

Losses 

15.5 / 16.1W 

At 3x400 / 480Vac 

Hold-up time 

25 / 25ms 

At 3x400 / 480Vac 

Temperature range 

-25 to +70°C 

 

Size 

(LxWxH)

 

272x182x70mm 

 

Weight 

1550g / 3.4lb 

 

 

Functional Diagram 

 

 

Output Characteristic 

 

 

Temperature Range 

Allowed output power

Ambient temperature

0W

-25

0

+70°C

150W

+55

300W

 

 

Hole Pattern for Mounting 

 

All dimensions in mm; connectors X1 to.X6 left to right 

 