FPS300.245-049-102
All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted.
Apr. 2022 / Rev. 0.2 FPS300-EN
6 / 28
DC-Input
The device is suitable to be supplied from a DC input voltage.
DC input
*)
nom.
DC 110-300 V
*)
±20 %
DC input range
min.
88 Vdc
max.
360 Vdc
DC input current
typ.
2.90 A
At 110 Vdc, at 24 V, 300 W
typ.
1.04 A
At 300 Vdc, at 24 V, 300 W
Turn-on voltage
Typ.
80 Vac
Shut-down voltage
Typ.
70 Vac
*)
For DC supply voltage above 150Vdc an external fuse with an appropriate rating is required. Wide range DC
input 110-300V without external fuse on request.
Fig. 4-1: Wiring for DC Input
Instructions for DC use:
a)
Use a battery or a similar DC source. A supply from the
intermediate DC-bus of a frequency converter is not
recommended and can cause a malfunction or damage the
unit.
b)
Cpole to L and –pole to N.
c)
Connect the PE terminal to an earth wire or to the machine
ground.
Input Inrush Current
An active inrush limitation circuit (NTCs, which are bypassed by a relay contact) limits the input inrush current after turn-on
of the input voltage.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
AC 100 V
AC 120 V AC 230 V
Inrush current
max.
2.18 A
peak
2.6 A
peak
6 A
peak
Fig. 5-1: Typical turn-on behavior at nominal load and 25 °C ambient temperature
Battery
Power Supply
DC
Load
AC
L
N
PE
+
-
+
-
250ms/DIV
Input Current 5A/DIV
Input Voltage
Output Voltage