UF40.241
UF-Series
24V,
40A,
160
MS
,
B
UFFER
M
ODULE
12.
E
FFICIENCY AND
P
OWER
L
OSSES
Efficiency
Typ.
>99%
Power supply mode, 40A output current,
capacitors fully charged
Power losses
Typ.
1.9W
Power supply mode, 0A output current,
capacitors fully charged
13.
L
IFETIME
E
XPECTANCY AND
MTBF
Calculated lifetime expectancy
*)
189
000h
*)
Stand-by mode, 40°C
536
000h
*)
Stand-by mode, 25°C
MTBF
**)
SN 29500, IEC 61709
2 114 000h
Stand-by mode, 40°C
3 937 000h
Stand-by mode, 25°C
MTBF
**)
MIL HDBK 217F
272 000h
Stand-by mode, 40°C, Ground Benign GB40
433 000h
Stand-by mode, 25°C Ground Benign GB25
95 000h
Stand-by mode, 40°C, Ground Fixed GF40
143 000h
Stand-by mode, 25°C Ground Fixed GF25
*) The
calculated lifetime expectancy
shown in the table indicates the minimum operating hours (service life) and is determined by the
lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according
to the capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15
years (131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices.
**)
MTBF
stands for
M
ean
T
ime
B
etween
F
ailure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit
has been running for 50 000h or only for 100h.
Oct. 2016 / Rev. 1.0 DS-UF40.241-EN
All parameters are specified at 24V, 40A, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
9/18