UF40.241
UF-Series
24V,
40A,
160
MS
,
B
UFFER
M
ODULE
14.
F
UNCTIONAL
D
IAGRAM
Fig. 14-1
Functional diagram
Buffer Capacitor
Charger &
Inrush Limiter
Buffer
Capacitor
Buffer Capacitor
Discharger
Status
LED
7 Active
6 (+)
Ready Monitor
+
-
Active Monitor
+
-
8 Ready
9 Inhibit
Opto-coupler
Buffer
Capacitor
Shut-Down
Input / Output
Voltage Monitor
Back-up
Level
Selector
Reverse-
Polarity
Protection
-
-
+
Safety and
Over-
Voltage
Protection
Chassis
Ground
Supply
Voltage
Opto-coupler
Opto-coupler
15.
T
ERMINALS AND
W
IRING
The terminals are IP20 finger safe constructed and suitable for field and factory wiring.
Supply voltage
Signals
Type
Screw terminals
Pluggable screw terminals
Solid wire
Max. 16mm
2
Max.
2.5mm
2
Stranded wire
Max. 10mm
2
Max.
2.5mm
2
American Wire Gauge
Max. AWG 22-8
AWG 22-14
Max. wire diameter
Max. 5.2mm (including ferrules)
2.25mm (including ferrules)
Wire stripping length
Typ. 12mm / 0.5inch
6mm / 0.25inch
Tightening torque
2.3Nm / 20.5lb.inch
0.4Nm / 3.5lb.inch
Screwdriver
3.5mm or 5mm slotted or
cross-head No 2
3mm slotted
Instructions:
a) Use appropriate copper cables that are designed for minimum operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C and
90°C for ambient up to 70°C minimum.
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Unused terminal compartments should be securely tightened or closed.
e) Ferrules are allowed.
Oct. 2016 / Rev. 1.0 DS-UF40.241-EN
All parameters are specified at 24V, 40A, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany