DC-UPS Instruction Manual for the DIMENSION UB10-Series 
Bedienungsanleitung für die DC-USV der DIMENSION UB10-Serie 

 

 
 

General Description 

The DIMENSION UB10-Series offer DIN-rail DC-UPS which bridge power outages for minutes by 
utilizing only one 12V battery for a 24V output. The UB10.241 has one 24V output while the 
UB10.245 has a DC/DC converter included which generates an additional 12V for various purposes. 

 

Gerätebeschreibung:

 

Die DC-USVs der DIMENSION UB10-Serie dienen zur Überbrückung von Netzausfällen im 
Minutenbereich, hierfür wird nur eine 12V Batterie benötigt. Das UB10.241 hat nur einen 24V 
Ausgang, während das UB10.245 noch einen zusätzlichen 12V Ausgang besitzt. 

 

Technical Data 

1)

 

Technische Daten 

1)

 

 

UB10.241 

UB10.245

 

 

 

Output Voltage Output 1 

Ausgangsspannung Ausgang 1 

nom. 

22.25V 

2)

 22.25V 

2)

 

 

Output Current Output 1 

Ausgangsstrom Ausgang 1 

nom. 

15A 

3)

 15A 

3)

 

 

 

 

nom. 

10/ 15A 

4)

 10/ 

15A 

4)

 

 

Output Voltage Output 2 

Ausgangsspannung Ausgang 2 

nom. 

N/A 

5)

 12.0V  

Output Current Output 2 

Ausgangsstrom Ausgang 2 

 

N/A 

5)

 5A 

 

Output Power 

(total)

 Ausgangsleistung 

(gesamt) 

 

240/ 360W 

6)

 240/ 

360W 

6)

 

 

Input Voltage 

Eingangsspannung 

 

DC 24V 

DC 24V 

 

Input Voltage Range 

Eingangsspannungsbereich 

 

22.5 – 30Vdc 

22.5 – 30Vdc 

 

Transfer Threshold Buffer Mode  Umschaltschwelle Pufferbetrieb 

 

22.25V 22.25V  

Allowed Batteries 

Erlaubte Batterien 

 

12V, VRLA 

12V, VRLA 

 

Allowed Battery Capacity 

Erlaubte Batteriekapazität 

 

3.9Ah – 27Ah 

3.9Ah – 27Ah 

 

Power Losses 

Verlustleistung 

typ. 

2.9/ 5.5W 

7)

 3.4/ 

6W 

7)

 

 

Operational Temperature 

Betriebstemperatur 

  -25 - +70°C 

-25 - +70°C 

 

Output Derating 

Leistungsrücknahme 

  6W/°C (60 - 70°C)  6W/°C (50 - 70°C)   

Storage Temp. Range 

Lagertemperaturbereich 

  -40 - +85°C 

-40 - +85°C 

 

Humidity Feuchte 

IEC60068-2-30 

5 - 95% r.H. 

8)

 

5 - 95% r.H. 

8)

 

 

Vibration Schwingen 

IEC 60068-2-6 

2g 2g  

Shock Schocken 

IEC60068-2-27  30g 6ms, 20g 11ms  30g 6ms, 20g 11ms   

Degree of Pollution 

Verschmutzungsgrad 

EN 50078 

2 2  

Degree of Protection 

Schutzart 

EN 60529 

IP20 IP20  

Over-temp. Protection 

Übertemperaturschutz 

 

Yes / Ja 

9)

 

Yes / Ja 

9)

 

 

Parallel Use 

Parallelschaltbar 

 

No / Nein 

No / Nein 

 

Serial Use 

Serienschaltbar 

 

No / Nein 

No / Nein 

 

Dimensions

)

 

(wxhxd)

 Abmessungen 

(BxHxT)

 

nom. 

49x124x117mm 

10)

49x124x117mm 

10)

 

Weight Gewicht 

max. 

530g / 1.17lb 

650g / 1.43lb 

 

Approvals Zulassungen 

 

 

11)

  

 

11)

  

 

Limited Warranty 

(Year)

 Gewährleistung 

 

(Jahre)

 

 

3 3  

 

1) 

All parameters are specified at 24Vdc input voltage, nominal output current, 25°C ambient and after a 5 
minutes run-in time unless otherwise noted. 

2) 

The output voltage is regulated to 22.25Vdc in a buffer event. In all other cases, the output voltage is 
approx. 0.3V lower than the input voltage assuming that the input voltage is sufficient and no overload is 
present.  

3) 

When no buffer event is present. 

4) 

During a buffer event 15A is available for the first 5 seconds. After this time, the output current is limited to 
10A. UB10.245: 12V output not loaded. 

5) 

Not applicable. 

6) 

The allowed total output power is 360W when no buffer event is present as well as for the first 5 seconds 
during a buffer event. After this, the allowed total output power is 240W. UB10.245: 12V output not loaded. 

7) 

At no load / 10A load, no buffer event is present. UB10.245: 12V output not loaded. 

8) 

Do not energize while condensation is present. 

9) 

Output shuts down with automatic restart. 

10) 

Depth without DIN-rail.  

11) 

See datasheet or markings on the unit. 

 

1) 

Alle Werte gelten bei 24Vdc Eingangsspannung, Nennausgangsstrom, 25°C Umgebung und nach 
einer Aufwärmzeit von 5 Minuten, wenn nichts anderes angegeben ist. 

2) 

Während eines Pufferfalls ist die Ausgangsspannung auf 22.25V geregelt. In allen anderen Fällen ist 
die Ausgangsspannung etwa 0,3V kleiner als die Eingangsspannung vorausgesetzt, dass die 
Eingangsspannung im spez. Bereich ist und kein Überlastfall vorliegt.  

3) 

Wenn kein Pufferfall vorliegt. 

4) 

Während eines Pufferfalls stehen für die ersten 5 Sekunden 15A zur Verfügung. Danach ist der 
Ausgangsstrom auf 10A begrenzt. UB10.245: Gilt bei 0A Last am 12V Ausgang. 

5) 

Nicht anwendbar. 

6) 

Die erlaubte Ausgangsleistung ist 360W wenn kein Pufferfall besteht oder während der ersten 5 
Sekunden eines Pufferfalls. Danach ist die erlaubte Ausgangsleistung 240W. UB10.245: Gilt bei 0A 
Last am 12V Ausgang. 

7) 

Bei Leerlauf / 10A Last und wenn kein Pufferfall besteht. UB10.245: 0A Last am 12V Ausgang. 

8) 

Nicht betreiben, solange das Gerät Kondensation aufweist. 

9) 

Ausgang schaltet ab und macht regelmäßig automatische Startversuche. 

10) 

Tiefe ohne DIN-Schiene. 

11) 

Siehe Datenblatt oder Prüfzeichen auf dem Gerät. 

 

Installation Procedure 

1. Use DIN-rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm. The unit is 

convection cooled. Do not obstruct air flow! Ventilation grid must be kept free of any obstructions. 

2. Connect the power supply to the input terminals of the DC-UPS. 
3. Connect the battery to the battery terminals of the DC-UPS. It is recommended to install the 

battery outside the cabinet or in a place where the battery will not be heated up by adjacent 
equipment. Use a 30A battery fuse typ ATO® 257 030 (Littelfuse) or similar in the battery path. 
The battery fuse protects the wires between the battery and the DC-UPS. It also allows the 
disconnection of the battery from the DC-UPS which is recommended when working on the 
battery or DC-UPS. Disconnect battery fuse before connecting the battery.  

4. Please note:  

Wires that are too small or too long between the DC-UPS and the battery can shorten the buffer 
time or can result in a malfunction of the DC-UPS. Do not use wires smaller than 2.5mm

2

 (or 

12AWG) and not longer than 2x1.5m (cord length 1.5m). Avoid voltage drops on this connection. 

5. Connect the buffered load to the output terminals of the DC-UPS. The output is decoupled from 

the input allowing load circuits to be easily split into buffered and non buffered sections. Non-
critical loads can be connected directly to the power supply and will not be buffered. The energy in 
the battery will be used in the circuits which require buffering. 

6. Set the end-of-charge voltage potentiometer and the buffer time limiter to an appropriate value. 
7. Install the fuse when the wiring is finished. Red LED on the DC-UPS should turn off. 

Terminals and Wiring 

The units are equipped with spring-clamp terminals for the power port and with a plug connector for 
the signal port. Use appropriate copper cables that are designed for an operating temperatures of 
60°C (for ambient up to 45°C) and 75°C (for ambient up to 60°C), minimum. Follow national 
installation codes and regulations! Ensure that all strands of a stranded wire enter the terminal 
connection! Ferrules are allowed, but not required. 

Power terminals: 

(except 12V output)

 

 

Solid wire / Stranded wire / American wire gauge:  0.5-6mm

/ 0.5-4mm

/ 20-10 AWG 

 

Wire stripping length:  10mm / 0.4inch 

 

Pull-out force (UL 486E):  10AWG: 80N, 12AWG: 60N 

12V output terminals: (For UB10.245 only) 

 

Solid wire / Stranded wire / American wire gauge:  0.1-2.5mm

/ 0.1-2.5mm

/ 28-12 AWG 

 

Wire stripping length:  8mm / 0.33inch 

 

Pull-out force (UL 486E):  10AWG: 80N, 12AWG: 60N 

Signal terminals: 

 

Solid wire / Stranded wire / American wire gauge:  0.2-1.5mm

/ 0.2-1.5mm

/ 22-14 AWG 

 

Wire stripping length:  6mm / 0.25inch 

 

Recommended tightening torque:  0.4Nm / 3.5lb.inch 

 

Installationsanleitung: 

1. Geeignet zur Montage an DIN-Schienen entsprechend EN 60715 oder EN 50022 mit einer 

Höhe von 7,5 oder 15mm. Das Gerät ist für Konvektionskühlung ausgelegt. Es ist für eine 
ungehinderte Luftzirkulation zu sorgen.  

2. Schließen Sie die Stromversorgung and die “Input” Klemmen der DC-USV an.  
3. Schließen Sie die Batterie an die “Battery” Klemmen der DC-USV an. Es wird empfohlen, die 

Batterie außerhalb des Schaltschranks oder so zu platzieren, dass diese nicht von 
benachbarten Geräten aufgeheizt wird. Verwenden Sie eine 30A Sicherung z.B. Typ ATO® 
257 030 (Littelfuse) o.ä. in dem Batterie-Pfad. Die Sicherung schützt die Kabelverbindung 
zwischen Batterie und DC-USV. Außerdem kann diese zur Trennung verwendet werden. 
Ziehen Sie die Sicherung heraus, bevor Sie die Batterie anschließen. 

4. Bitte beachten Sie: Zu dünne oder zu lange Kabel zwischen DC-USV und Batterie können die 

Pufferzeit verkürzen oder zum Fehlverhalten der DC-USV führen. Benutzen Sie keine 
Anschlussdrähte kleiner als 2,5mm

2

 und nicht länger als 2x1,5m (Kabellänge 1,5m).  

5. Schließen Sie die zu puffernde Last an die „Output“ Klemmen an. Der Ausgang ist vom 

Eingang entkoppelt. So kann man Lasten in gepufferte und ungepufferte Zweige aufteilen. 
Unkritische Lasten können ungepuffert direkt an die Stromversorgung angeschlossen 
werden. So wird die Energie der Batterie nur für zu puffernde Lasten verwendet. 

6. Stellen Sie am "End-of-Charge-Voltage" Einsteller (Ladeschlussspannung) und "Buffer-Time-

Limiter" Einsteller (Pufferzeit-Begrenzer) den entsprechenden Wert ein. 

7. Schließen Sie die Sicherung an, wenn alle Arbeiten an der Batterie oder DC-USV beendet 

sind. Nach dem Einschalten muss die rote LED erlöschen. 

Anschlussklemmen und Verdrahtung 

Die Geräte sind mit Schnellanschluss-Federkraftklemmen ausgestattet. Verwenden Sie 
geeignete Kupferkabel, die mindestens für 60°C (bei einer Umgebungstemperatur bis zu 45°C) 
und 75°C (bei einer Umgebungstemperatur bis zu 60°C) zugelassen sind. Beachten Sie 
nationale Bestimmungen und Installationsvorschriften! Stellen Sie sicher, dass keine einzelnen 
Drähte von Litzen abstehen. Aderendhülsen sind erlaubt, aber nicht erforderlich. 

Leistungsanschlussklemmen: 

(außer 12V Ausgang)

 

 

Starrdraht / Litze / Amerikanischer Querschnitt:  0,5-6mm

/ 0,5-4mm

/ 20-10 AWG 

 

Abisolierlänge:  10mm / 0,4inch 

 

Abziehkraft (UL 486E):  10AWG: 80N, 12AWG: 60N 

Klemmen für 12V Ausgang: (Nur bei UB10.245) 

 

Starrdraht / Litze / Amerikanischer Querschnitt:  0,1-2,5mm

/ 0,1-2,5mm

/ 28-12 AWG 

 

Abisolierlänge:  8mm / 0,33inch 

 

Abziehkraft (UL 486E):  10AWG: 80N, 12AWG: 60N  

Signalklemmen: 

 

Starrdraht / Litze / Amerikanischer Querschnitt:  0,2-1,5mm

/ 0,2-1,5mm

/ 22-14 AWG 

 

Abisolierlänge:  6mm / 0,25inch 

 

Empfohlenes Anzugsdrehmoment:  0,4Nm / 3.5lb.inch 