QTD20.241
Q-Series
24V,
20A,
DC
I
NPUT
11.
T
ERMINALS AND
W
IRING
The terminals are IP20 Finger safe constructed and suitable for field and factory wiring.
Type
Quick-connect spring-clamp terminals
Solid wire
Max. 6mm
2
Stranded wire
Max. 4mm
2
American Wire Gauge
Max. AWG10
Wire diameter
Max. 2.8mm (including ferrules)
Wire stripping length
Typ. 10mm / 0.4inch
Screwdriver Not
applicable
Recommended tightening torque Not
applicable
Instructions:
a) Use appropriate copper cables that are designed for minimum
operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C minimum
90°C for ambient up to 70°C minimum.
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal
connection!
d) Do not use the unit without PE connection.
e) Ferrules are allowed.
1.
Insert the wire
2.
Snap the lever
To disconnect wire: same procedure
vice versa
Daisy chaining:
Daisy chaining (jumping from one DC/DC converter output to the next) is allowed as long as the average output
current through one terminal pin does not exceed 27A. If the current is higher, use a separate distribution terminal
block as shown in Fig. 11-2.
Fig. 11-1 Daisy chaining of outputs
Fig. 11-2 Using distribution terminals
Load
+
-
DC/DC
converter
+ +
- -
Output
DC/DC
converter
+ +
- -
Output
max 27A
continuous!
Distribution
Terminals
Load
+
-
DC/DC
converter
+ +
- -
Output
DC/DC
converter
+ +
- -
Output
Oct. 2016 / Rev. 2.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
11/27