QTD20.241
Q-Series
24V,
20A,
DC
I
NPUT
3.
I
NPUT
Input nom.
DC
600V
-20%/+40%
Input range
min.
480-840Vdc Continuous
operation
min.
360-480Vdc
Maximal 60s or with reduced output current, see Fig. 5-2
min.
840V-900Vdc
Maximal 60s or with reduced output current, see Fig. 5-2
max.
1000Vdc
Absolute maximum input voltage with no damage to
the DC/DC converter. Above 900Vdc, the output will
switch off and will turn-on again, when the input
voltage falls below 850Vdc.
Allowed voltage input to Earth
max.
600V R.M.S.
Continuous, IEC 60664-1
max.
±900Vpk
Peak value, allowed for transients
Slew rate for voltages between
input and Earth (ground)
max. 1000V/μs
Allowed input ripple voltage
max.
50Vpp
50Hz-40kHz
Turn-on voltage
typ.
450Vdc
Steady-state value, load independent, see Fig. 3-1
Shut-down voltage
typ.
325Vdc
Steady-state value, load independent, see Fig. 3-1
Input current
typ.
0.79A
Start-up delay
typ.
350ms
Rise time
typ.
70ms
At 24V, 20A, only resistive load see Fig. 3-2
typ.
110ms
At 24V, 20A, resistive load with an additional 20mF
capacitor
Turn-on overshoot
max.
500mV
External capacitors on input
Allowed without any limitations
Fig. 3-1
Input voltage range
Turn-on
450Vdc
V
IN
P
OUT
900Vdc
Shut
-down
840Vdc
325Vdc
480Vdc
360Vdc
A: continuously allowed
B: < 60s or with derating
B
A
B
Fig. 3-2
Turn-on behavior, definitions
Fig. 3-3
Input current vs. output load at 24V
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Intput
Voltage
20A
2
4
6
8 10 12 14 16 18
0
0.2
0.4
0.6
1.0A
0.8
Output Current
Input Current, typ.
Oct. 2016 / Rev. 2.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
4/27