background image

 

 

PISA11.CLASS2

 

 

 

PISA11-Series 

P

ROTECTION 

M

ODULE 

24V,

 

4

 

O

UTPUTS

 

 

 

7.

 

C

ONNECTING 

C

APACITIVE 

L

OADS TO THE 

O

UTPUTS

 

 

Large input capacitors of drives, monitors or other similar loads can result in an unintended shutdown of the module 
when trying to turn-on such loads. This especially can occur after a reset or by turning on a load via the push button or 
the external signal input. The PISA protection module is designed to be exceptionally compatible with such types of 
loads. The module can turn-on as much capacitance as possible and comprises several different protection mechanisms 
to protect against an unintended shutdown or damage of the unit. 

The permissible capacitor sizes which can be connected to the output of the PISA module depends on the load current 
itself as well as on the characteristic of the load. 

The following tables show two typical cases (case A and case B) for the permissible capacitors, which can be connected 
on the outputs without shutdown of the protection module. The listed values are valid for the entire temperature 
range. 

 

Case A: All outputs are loaded. 

The minimum values are worst-case figures for the permissible capacitors which are defined with an additional 
constant current load and with the maximum permissible total current of the PISA protection module. See also the 
parameter list below the table. 

The typical values are defined with an additional resistive load. See also the parameter list below the table. 

 

Permissible Capacitors 

 

PISA11.CLASS2 

 

Per channel 

 

58mF 

 

  

14mF 

 

All four outputs together 

typ. 

58mF 

 

 min. 

14mF 

 

Parameters:  

Typical values are with an additional 1.9A resistive load per output. 

Minimum values are with an additional 3.7A constant current load per output.

 

 

Case B: Only one output is loaded 

The minimum values for the permissible capacitors are defined with an additional constant current load according to 
the parameter list below. During the tests, only one output is loaded and all others are not.  

The typical values for the permissible capacitors are defined with an additional resistive load according to the 
parameter list below. During the tests, only one output is loaded and all others are not. 

 

Permissible Capacitors 

 

PISA11.CLASS2 

 

Per channel 

typ. 

68mF 

 

 min. 

45mF 

 

Parameters:  

Typical values are with an additional 1.9A resistive load. Minimum values are with an additional 3.7A constant current 

load. 
 

 

Fig. 7-1

   Test setup for capacitive load measurements 

 

 

Power
Supply

24V,
min. 40A

-

+

PISA11

Protection

Module

Out-1

+

-

-

Out-2

Out-3

Out-4

8/19

Distribution Node

1m, 2.5mm

2

1m, 2.5mm

2

4x R

Sense

10mOhm

R / I

Load

R / I

Load

R / I

Load

R / I

Load

1m, 1.5mm

2

1m, 1.5mm

2

1m, 1.5mm

2

1m, 1.5mm

2

0.3m, 1.5mm

2

0.3m, 1.5mm

2

0.3m, 1.5mm

2

0.3m, 1.5mm

2

1m, 2.5mm

2

 

 

Feb. 2012 / Rev. 1.3  DS-PISA11.CLASS2 - data sheet - 
All parameters are specified at 24Vdc input, 25°C ambient temperature and a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278-0    Germany 

Summary of Contents for Dimension PISA11 Series

Page 1: ...n they are connected directly to the same power supply as the PISA module Less critical loads that are not affected to short voltage interruptions or that could even be the cause of a fault on the 24V...

Page 2: ...6 1 ZM3 WALL Wall Mounting Bracket 19 The information presented in this document is believed to be accurate and reliable and may change without notice The housing is patent by PULS US patent No US D44...

Page 3: ...ly so much current that the input voltage does not drop below 21V In case the input voltage would fall below this value e g due to overloads too small of a power supply or high inrush currents such as...

Page 4: ...n power off before working on the device Protect against inadvertent re powering Make sure that the wiring is correct by following all local and national codes Do not modify or repair the unit Do not...

Page 5: ...see Fig 5 1 output 3 nom 3 7A 3 2A see Fig 5 1 output 4 nom 3 7A 3 2A see Fig 5 1 All 4 outputs together nom 14 8A 12 8A Output current limitation min 16 6A 16 6A typ 19 9A 19 9A max 23 6A 23 6A Volt...

Page 6: ...d output current At 2 times the rated current typ 1s at 7 4A At short circuit typ 10ms The timer for shutdown starts immediately once the rated current levels are exceeded All output channels will shu...

Page 7: ...All four outputs will shutdown simultaneously Shutdown times for a short circuit condition across the outputs can be found in Fig 6 2 Fig 6 2 Active current limitation Period of time in current limit...

Page 8: ...al values are defined with an additional resistive load See also the parameter list below the table Permissible Capacitors PISA11 CLASS2 Per channel 58mF 14mF All four outputs together typ 58mF min 14...

Page 9: ...max 10Vdc reset Galvanic isolation nom 500Vac Test voltage signal path to power path 10 SYNCHRONIZATION OF MULTIPLE PISA MODULES If multiple PISA modules are used on the same power supply it is recomm...

Page 10: ...his feature is also called return voltage immunity or resistance against Back E M F Electro Magnetic Force The protection module is resistant and does not show malfunctioning when a load feeds back vo...

Page 11: ...ulated according to the capacitor s manufacturer specification The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years 131 400h Any number exceeding this value...

Page 12: ...rotection function of the input voltage protection circuit all other modules will shutdown too This avoids a false interpretation of which output channel caused the problem If the cause for the shutdo...

Page 13: ...a Use NEC Class 2 rated wires for the output b Use appropriate copper cables that are designed for minimum operating temperatures of 60 C for ambient up to 45 C and minimum 75 C for ambient up to 60...

Page 14: ...ge voltage on input lines EN 61000 4 5 DIN Rail 500V 1kV 500V 1kV Criterion A Criterion A Surge voltage on output lines EN 61000 4 5 DIN Rail 500V 1kV 500V 1kV Criterion A Criterion A Surge voltage on...

Page 15: ...y III IEC 62103 EN 50178 altitudes up to 2000m II for altitudes from 2000m to 6000m Degree of pollution 2 IEC 62103 EN 50178 not conductive Operational temperature is the same as the ambient temperatu...

Page 16: ...F signal input and input output voltage are 1 3mm The following dielectric strength tests were conducted Fig 20 1 Dielectric strength A B C Type test 60s 500Vac 500Vac 50Vac Factory test 5s 500Vac 500...

Page 17: ...rrent Protector Component Recognition UL Category QVRQ2 E File E342020 ANSI ISA 12 12 01 2007 Class I Div 2 Pending LISTED for use in Hazardous Location Class I Div 2 T4 Groups A B C D systems NRTL C...

Page 18: ...r PBDE Polychlorinated Diphenylether PCDE Polydibromphenyl Oxyd PBDO Cadmium Asbestos Mercury Silicia 24 READ OUT OF THE SOFTWARE REVISION LEVEL PISA utilizes a microcontroller with a dedicated firmwa...

Page 19: ...AL DIMENSIONS AND WEIGHT Weight 120g 0 26lb DIN Rail Use 35mm DIN rail according to EN 60715 or EN 50022 with a height of 7 5 or 15mm The DIN rail height must be added to the unit depth to calculate t...

Reviews: