Puls Dimension CP Series Manual Download Page 16

CP20.245-R2 

CP-Series 

24V,

 

20A,

 

S

INGLE 

P

HASE 

I

NPUT

 

Aug. 2022 / Rev 1.1 DS-CP20.245-R2 EN  

All parameters are typ. values specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

16/28 

Switching Frequencies 

The power supply has two converters with two different switching frequencies included. 

Switching frequency 1 

70kHz to 130kHz 

PFC converter, input voltage and output power dependent 

Switching frequency 2 

80kHz to 140kHz 

Main converter, output power dependent 

16. E

NVIRONMENT

Operational temperature

1)

 

-40°C to +70°C

Reduce output power according Fig. 16-1 

Storage temperature 

-40°C to +85°C

For storage and transportation 

Output derating

4)

 

12W/K

+60°C to +70°C

Humidity

2)

 

5 to 95% r.h. 

IEC 60068-2-30 

Atmospheric pressure 

110-80kPa
80-47kPa

De-rating requirements of Fig. 16-2 apply 

Altitude 

Up to 2000m   

Without any restrictions 

2000 to 6000m   

Derating

4)

 requirements of Fig. 16-2 apply 

Altitude derating

4)

 

30W/1000m or 5K/1000m 

Above 2000m , see Fig. 16-2 

Over-voltage category 

III 

acc. IEC 61010-2-201, altitudes up to 2000m 

II 

acc. IEC 61010-2-201, altitudes up to 6000m 
and atmospheric pressures from 80-47kPa 

Degree of pollution 

acc. IEC 61010-2-201, not conductive 

Vibration sinusoidal

3)

 

2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis

IEC 60068-2-6 

 Shock

3)

 

30g 6ms, 20g 11ms
3 bumps / direction, 18 bumps in total

IEC 60068-2-27 

LABS compatibility 

The unit does not release any silicone or other LABS-critical substances and is suitable for 
use in paint shops. 

Audible noise 

Some small audible noise will be emitted from the power supply 

1) Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2cm below the unit.
2) Do not energize while condensation is present
3) Tested in combination with DIN-Rails according to EN 60715 with a height of 15mm and a thickness of 1.3mm and standard orientation.
4) The de-rating is not hardware controlled. The customer has to take care by himself to stay below the de-rated current limits in order not to

overload the unit.

Fig. 16-1

   Output current vs. ambient temp. 

(

I

nom = 20A; 

I

out with PowerBoost = 24A) 

Fig. 16-2

   Output current vs. altitude 

Allowed Output Current

0

-40

0

20

40

70°C

4A

8A

12A

16A

20A

24A

60

B

A

Ambient Temperature

A... continuous
B... short term (max. 5s)

2000m

4000m

6000m

4A

8A

12A

16A

20A

24A

Altitude

Allowed Output Current

B

C

A... Tamb < 60°C

B... Tamb < 50°C

C... Tamb < 45°C

D... Short term

A

D

AP

*)

80kPa

62kPa

47kPa

110kPa

0m

*) Atmospheric pressure

Summary of Contents for Dimension CP Series

Page 1: ...systems and plug connector terminals to allow device replacement while the application keeps running The CP20 245 R2 covers an extreme wide temperature range from 40 C up to 60 C providing full outpu...

Page 2: ...ed Enclosure 28 24 12 Mounting Orientations 29 The information given in this document is correct to the best of our knowledge and experience at the time of publication If not expressly agreed otherwis...

Page 3: ...ons require a reduction in output current Make sure that the wiring is correct by following all local and national codes Use appropriate copper cables that are designed for a minimum operating tempera...

Page 4: ...me unless otherwise noted www pulspower com Phone 49 89 9278 0 Germany 4 28 The maximum surrounding air temperature is 70 C The operational temperature is the same as the ambient or surrounding air te...

Page 5: ...1 65 1 63 1 63 At 20A Start up delay typ 450ms 420ms 440ms See Fig 3 2 Rise time typ 145ms 145ms 145ms At 20A const current load 0mF load capacitance see Fig 3 2 typ 160ms 160ms 160ms At 20A const cur...

Page 6: ...r Supply AC DC Battery N a Use a battery or a similar DC source A supply from the intermediate DC bus of a frequency converter is not recommended and can cause a malfunction or damage the unit b Conne...

Page 7: ...see Fig 6 3 The output voltage stays above 20V See chapter 24 1 for more peak current measurements Overload behaviour Continuous current Output voltage 13Vdc see Fig 6 1 HiccupPLUS mode Output voltage...

Page 8: ...c behavior 12ms 0 0 4 8 12 28V 16 20 24 70A 30 10 40 50 20 60 Output Current 7 HOLD UP TIME AC 100V AC 120V AC 230V Hold up Time typ 65ms 65ms 65ms At 10A see Fig 7 1 min 54ms 54ms 54ms At 10A see Fig...

Page 9: ...power supply in front of the decoupling device see also chapter 11 Contact closes As soon as the output voltage reaches typ 22Vdc Contact opens As soon as the output voltage dips below 22Vdc Short di...

Page 10: ...n assumption for a typical application where the power supply is loaded with 25 of the nominal load for 25 of the time 50 of the nominal load for another 25 of the time 75 of the nominal load for anot...

Page 11: ...ectrolytic capacitors Lifetime expectancy is specified in operational hours and is calculated according to the capacitor s manufacturer specification The manufacturer of the electrolytic capacitors on...

Page 12: ...mm2 max 6mm2 max 1 5mm2 American Wire Gauge AWG 20 12 AWG 24 10 AWG 26 14 Max wire diameter 2 4mm including ferrules 3 2mm including ferrules 1 8mm including ferrules Recommended tightening torque max...

Page 13: ...system is running Load I I L N PE 1a L N PE CP20 241 R2 73 Power Supply DC OK DC OK Output 24V 20A Input L N PE CP20 241 R2 73 Power Supply DC OK DC OK Output 24V 20A Input 1b 2a 3a 3b 2b Instructions...

Page 14: ...8 0 Germany 14 28 14 FRONT SIDE AND USER ELEMENTS Fig 14 1 Front side A Input Terminals plug connector N L Line input PE Protective Earth input B Output Terminals plug connector Positive output Negati...

Page 15: ...Criterion C Criterion A Criterion A Criterion A Criterion A Voltage interruptions EN 61000 4 11 0 of 200Vac 0V 5000ms Criterion C Voltage sags SEMI F47 0706 Dips on the input voltage according to SEMI...

Page 16: ...heric pressures from 80 47kPa Degree of pollution 2 acc IEC 61010 2 201 not conductive Vibration sinusoidal3 2 17 8Hz 1 6mm 17 8 500Hz 2g 2 hours axis IEC 60068 2 6 Shock3 30g 6ms 20g 11ms 3 bumps dir...

Page 17: ...y critical situations e g customer does not care about de rating requirements ambient temperature too high obstructs the airflow or install the unit in unsuitable mounting orientation There is no corr...

Page 18: ...ng set the cut off current settings to the value in the table below Fig 19 1 Dielectric strength A B C D A D C B B N L Input DC ok Earth PE Output Type test 60s 2500Vac 3000Vac 1000Vac 500Vac Factory...

Page 19: ...ble for US and Canada E File E198865 ATEX Agency Certificate Bureau Veritas EN 60079 0 Explosive atmospheres General requirements EN 60079 7 EN 60079 15 Equipment protection by type of protection e an...

Page 20: ...according to VDMA 24364 C1 L W for solvents and water based paints 21 REGULATORY PRODUCT COMPLIANCE CE EU Declaration of Conformity Trade conformity assessment for Europe The CE mark indicates conform...

Page 21: ...GHT Width 48mm Height 124mm without plug connectors Depth 127mm without plug connector The DIN rail depth must be added to the unit depth to calculate the total required installation depth DIN Rail Us...

Page 22: ...23 ACCESSORIES 23 1 ZM10 WALL WALL PANEL MOUNT BRACKET This bracket is used to mount the devices on a wall panel without utilizing the DIN Rail The bracket can be mounted without detaching the DIN ra...

Page 23: ...to trip fuses on faulty output branches or to start peak current demanding loads Solenoids contactors and pneumatic modules often have a steady state coil and a pick up coil The inrush current demand...

Page 24: ...haracteristic a setting to 24 0V results to an output voltage of 23 8V 0 2 at 24A and 25 0V 0 2 at no load See Fig 24 3 Output current min 24A At 45 C min 20A At 60 C min 15A At 70 C Reduce output cur...

Page 25: ...AC supply systems and may also be used on 24V branches MCB s are designed to protect wires and circuits If the ampere value and the characteristics of the MCB are adapted to the wire size that is used...

Page 26: ...load sharing between power supplies connected in parallel The Parallel use mode regulates the output voltage in such a manner that the voltage at no load is approx 4 higher than at nominal load See al...

Page 27: ...individual power supply units Therefore use the built in DC OK relay contact of the power supply Fig 24 7 Wiring diagram 1 1 Redundancy for 20A output current 24V 20A Load L N PE Failure Monitor I I L...

Page 28: ...phase to phase connection is allowed as long as the supplying voltage is below 240V 10 24 11 USE IN A TIGHTLY SEALED ENCLOSURE When the power supply is installed in a tightly sealed enclosure the temp...

Page 29: ...nded output current Curve A2 Max allowed output current results in approximately half the lifetime expectancy of A1 Fig 24 9 Mounting Orientation A Standard orientation Power Supply OUTPUT INPUT Outpu...

Reviews: