CPS20.241-60 Installation Manual 

 

 

 

Product Description 

The CPS20.241-60 is a DIN-rail mountable DC/DC converter with conformal coated pc-boards of the 
DIMENSION series. It provides a floating, stabilized and galvanically separated SELV/PELV output 
voltage. 
The output of the device is equipped with a decoupling MOSEFT for 1+1 and n+1 redundant use. 
 

Intended Use 

This device is designed for installation in an enclosure and is intended for use in rolling stock 
equipment for railway applications according to EN 50155 or for use in industrial control, process 
control, monitoring and measurement equipment or the like. Do not use this device in equipment, 
where malfunction may cause severe personal injury or threaten human life. 
 

Installation Instructions 

Install the device in an enclosure providing protection against electrical, mechanical and fire hazards. 
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the 
device. Other mounting orientations require a reduction in output current. 
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper 
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up to 
+45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C. 
Ensure that all strands of a stranded wire enter the terminal connection. 
The device is designed for pollution degree 2 areas in controlled environments. No condensation or 
frost is allowed. 
The enclosure of the device provides a degree of protection of IP20. 
The device is designed as “Class of Protection I” equipment according to IEC 61140. 
Do not use without a proper PE (Protective Earth) connection. 
The device can be powered from a regulated power supply or a similar DC source. The voltage 
between the supply voltage terminals and ground must not exceed 375Vdc continuously. 
A disconnecting means shall be provided for the input of the device. 
The device is designed for convection cooling and does not require an external fan. Do not obstruct 
airflow and do not cover ventilation grid! 
The device is designed for altitudes up to 6000m (19685ft). See additional requirements in the product 
datasheet for use above 2000m (6560ft). 
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and 
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device 
is permanently loaded with less than 50%, the 5mm can be reduced to zero. 
The device is designed, tested and approved for branch circuits up to 32A (IEC) and 30A (UL) without 
additional protection device. If an external fuse is utilized, do not use circuit breakers smaller than 10A 
B- or C-Characteristic to avoid a nuisance tripping of the circuit breaker. 
The maximum surrounding air temperature is +85°C (+185°F). The operational temperature is the 
same as the ambient or surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 5% and 95% relative humidity. 
Check for correct input polarity. The device will not operate when the voltage is reversed. 
 

Functional Description 

The output is electronically protected against no-load, overload and short circuit and can supply any 
kind of loads, including unlimited inductive loads and capacitive loads. If capacitors with a capacitance 
>0.5F are connected, the unit might charge the capacitor in an intermittent mode. 
Do not apply return voltages from the load to the output higher than 35V. 
The green DC-OK LED reports an output voltage above 22V, which is produced by the device itself. 
The DC-OK relay monitors the output voltage and the contact is closed when the DC-OK LED is on. 
Contact ratings: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A for resistive loads. 
The device is equipped with an over-temperature protection. In case of a high temperature, the output 
shuts down and starts automatically again after cooling off. 
At heavy overloads (when output voltage falls below 13V), the device delivers continuous output 
current for 2s. After this, the output is switched off for 18s before a new start attempt is automatically 
performed. This cycle is repeated as long as the overload exists. 
Devices can be paralleled to increase the output power. The ambient temperature is not allowed to 
60°C. The device is featured with a "soft output regulation characteristic" in order to achieve 
current share between multiple devices, when they are connected in parallel. The "soft output 
regulation characteristic" regulates the output voltage in such a manner that the voltage at no load is 
approx. 2% higher than at nominal load. Energize all units at the same time. It also might be 
necessary to cycle the input power (turn-off for at least five seconds), if the output was in overload or 
short circuit. 
Same devices can be connected in series for higher output voltages. It is allowed to connect as many 
devices in series as needed, providing the sum of the output voltage does not exceed 150Vdc. 
In case of an internal defect, a redundant circuit limits the maximum output voltage to 32V. The output 
shuts down and automatically attempts to restart. 

 

Technical data

 

All values are typical figures specified at 110Vdc input voltage, 24V 16.3A 
output load, 25°C ambient temperature and after a 5 minutes run-in time 
unless otherwise noted. 

Output voltage 

DC 24V 

0%/+6% 

Adjustment range 

- Not 

adjustable 

Output current 

16.3A Continuous 

below 

+70°C

 

16.3A 

For 10 minutes at +85°C

Input voltage DC 

DC 110V 

-30% / +40% 

Input current DC 

3.87A  

Input inrush current 

6A pk 

 

Efficiency 

93.7%  

Power losses 

26.9W  

Hold-up time 

35ms  

Temperature range 

-40 to +85°C 

 

Max. wire size (litz wire) 

4mm² Power 

terminals 

Wire size AWG 

AWG 20-10 

Power terminals 

Max. wire diameter 

2.8mm Power 

terminals 

Wire stripping length 

10mm / 0.4inch 

Power terminals 

Max. wire size (litz wire) 

1.5mm²

 

 Signal 

terminals 

Wire size AWG 

AWG 26-14 

Signal terminals 

Max. wire diameter 

1.5 mm 

Signal terminals 

Wire stripping length 

7mm / 0.28inch 

Signal terminals 

Size (wxhxd) 

65x124x127mm Without 

DIN-rail 

Weight 

980g / 2.16lb 

 

 
 

Functional diagram 

+

+

-
-

DC-OK
contact

Output

Over-

Voltage

Protection

Output

Voltage

Regulator

Output

Filter

DC-ok
Relay

Output

Voltage
Monitor

Output

Power

Manager

Temper-

ature

Shut-

down

DC-OK

LED

Power

Converter

De-

coupling

Input Fuse
Input Filter
Active
Inrush
Limiter

+

-

Reverse

Polarity

&

Back-

feeding

Protection

Boost

Converter

 
 

Output characteristic 

Output voltage

25A

24V

Output current

12V

0V

5A

10A

15A

20A

0A

A: continuous current
B: intermitted current

A

B

 

 
 

Temperature range 

Allowed output current

Ambient temperature

6A

0A

-40°C

A: 100-154Vdc continuous
B: 77-100Vdc continuous
C: up to 10 minutes

16.3A

+25°C

0°C

+50°C

+70°C

+85°C

12A

C

B

A

 

 