-17-
4.3
DC input wiring
1.
DC input connection please refer to AC input installation rules.
2.
Connection way and position, please refer to figure 17.
Model
Max. Battery
current
Battery cable
Terminal
specification
1KVA(48Vdc)
25A
12AWG
5.5-5
2KVA(48Vdc)
50A
10AWG
5.5-5
3KVA(48Vdc)
75A
10AWG
5.5-5
1KVA
6A
12AWG
5.5-5
2KVA
12A
10AWG
5.5-5
3KVA
18A
10AWG
5.5-5
4KVA
25A
10AWG
5.5-5
6KVA
37A
10AWG
5.5-5
8KVA
50A
8AWG
10-6
10KVA
60A
6AWG
16-6
12KVA
75A
6AWG
16-6
15KVA
90A
4AWG
25-6
20KVA
120A
4AWG
25-6
Table 3
BATT-
BATT+
Figure 17