31
15.10. FLUE AND BAROMETRIC DRAFT CONTROL CONNECTION
Before connecting the stove pipe, make sure you have removed any accessory from the flue
pipe such as the scraper, shovel, and the poker.
The flue outlet on the Max Caddy add-on is 6" in diameter must be installed with a 6" chimney approved for use with
wood burning heating appliances (2100°F). If the draft exceeds 0.06 IN.W.C., a barometric control must installed.
Never install a manual damper.
Secure the exhaust pipe to the flue adapter with three screws.
For a proper installation, follow the advice below:
•
All the exhaust pipe joints must be secured with three screws.
•
Make sure that each screw goes through the inner wall of both connectors (male and female). See pictures below
showing a male-female coupling.
•
A minimum rise of ¼" per horizontal foot must be respected.
PROPER INSTALLATION
IMPROPER INSTALLATION
CAUSES RESTRICTION
FLUE
ADAPTER