PSA Lifesaver HA240 Installation And User Manual Download Page 4

3

6. MOUNTING INSTRUCTIONS 

A trim ring is provided on the back of the Heat Alarm. This trim ring is removed by holding the trim ring and twist-
ing the Heat Alarm in the direction indicated by the TURN TO REMOVE arrow. The trim ring is secured to the
heat alarm by a trim lever.  

CAUTION ! THE COVER IS A SEALED UNIT AND HAS NO REMOVABLE 

SERVICEABLE  PARTS ! DO NOT TAMPER.

6.1           Secure a suitable junction box near the position of the Heat Alarm, ensure the quick connect cable length

is long enough to reach the junction box for termination to be made.

6.2           Connect Active, Neutral and Switch line to the Heat Alarm cable using the terminal connection block pro-

vided.  Secure these terminals inside the junction box. 

6.3           Punch out the suitable fixing holes on the trim ring and then pull the AC connector through the centre of

the trim ring.

6.4           Secure the trim ring to the ceiling using the fixing holes provided.Connect the 9V battery (back up) into

the battery compartment. Now, plug in the AC connector into the back of the Heat Alarm.  Ensure the
locks on the AC connector snaps firmly into place.

6.5           Now mount the heat alarm onto the trim ring. Rotate the heat alarm until the heat alarm snap firmly into

place.

NOTE:PLEASE ENSURE THAT BATTERY IS INSTALLED PRIOR TO MOUNTING OF HEAT ALARM

Switch on the A.C. power and the green A.C. power ‘ON’ indicator should be lit. The Heat Alarm is now operating
on mains power.

A

N

FUSE OR CIRCUIT BREAKER

RED

WHITE

BLACK

A

SW

N

RED

WHITE

BLACK

A

SW

N

RED

WHITE

BLACK

A

SW

N

RED

WHITE

BLACK

5.4           The maximum wire run distance between the first and last unit in an interconnected system is 307 metres.

Figure 1 illustrates interconnection wiring. Improper connection will result in damage to the alarm,  failure
to operate, or electrical shock hazard.

5.6          Make certain alarms are wired to a continuous (non-switched) final sub-circuit.

Note: Use approved listed Australian Standards cable 1.0mm² TPS or larger as 

required by local codes.

FIGURE 1 “INTERCONNECT WIRING DIAGRAM”

ALARM HARNESS  --------------------CONNECTED TO:
BLACK

-------------------------------N

WHITE

-------------------------------SW

RED

-------------------------------A

FIGURE 1: TYPICAL DIAGRAM SHOWING INTERCONNECTION OPTIONS

1004-7201-01(HA240)_V2:_  2010.9.2  9:20 AM  Page 4

Summary of Contents for Lifesaver HA240

Page 1: ... and or multiple station 24 units maximum The heat alarm is designed to activate at 73 C when the temperature range is between 58 C and 88 C Temperature rating 73 C 163 4 F Fixed temperature only Maximum ambient 88 C 190 4 F temperature at heat alarm Recommended coverage 230 square metres Note A Recommended spacing 15 3 metres Maximum distance from wall 7 6 metres Note B Note A Maximum coverage is...

Page 2: ...alled within rooms may be necessary BEDROOM ATTIC BEDROOM HEAT ALARM IONISATION SMOKE ALARM PHOTOELETRIC SMOKE ALARM KITCHEN LIVING ROOM GARAGE UTILITY LAUNDRY 2 2 The most favourable mounting location for a Heat Alarm is on the ceiling and in the centre of the room At this location the alarm is closest to all areas of the room EXCEPTION When the mounting surface might become considerably warmer o...

Page 3: ...ir conditioning near ceiling fans or other high air flow areas 3 2 In an area where the temperature may fall below 5 C 41 F or rise above 88 C 190 4 F 3 3 Near fluorescent lights electronic noise may cause nuisance alarms Diagram C 4 INSTALLATION INSTRUCTIONS PLEASE READ CAREFULLY 4 1 This Heat Alarm should be installed with an AS approved junction box All connections must be installed by a qualif...

Page 4: ... in the AC connector into the back of the Heat Alarm Ensure the locks on the AC connector snaps firmly into place 6 5 Now mount the heat alarm onto the trim ring Rotate the heat alarm until the heat alarm snap firmly into place NOTE PLEASE ENSURE THAT BATTERY IS INSTALLED PRIOR TO MOUNTING OF HEAT ALARM Switch on the A C power and the green A C power ON indicator should be lit The Heat Alarm is no...

Page 5: ...per second The rapid flashing LED and pulsating alarm will continue until the temperature drops below 73 C 163 4 F WHEN HEAT ALARMS ARE INTERCONNECTED with compatible Smoke Alarms only the Red LED of the originating unit will flash rapidly All other units in the interconnect system will sound an alarm but their Red LED s will not flash TESTING Test by pushing the test button on the cover and hold ...

Page 6: ...your alarm by using a vacuum cleaner hose and vacuuming around the heat sensing element and the perimeter of the alarm The outside of the alarm can be wiped with a damp cloth We recommend a periodic monthly inspection and cleaning of the Heat Alarm to ensure proper operation AFTER CLEANING REINSTALL YOUR ALARM AND TEST YOUR ALARM BY USING THE TEST BUTTON AND CHECK THAT THE GREEN LED IS ON 12 LIMIT...

Page 7: ...s defective in any way do not tamper with the unit Return it to PSA Products Pty Ltd 17 Millicent Street Burwood Victoria 3125 16 1 PSA Products Pty Ltd warrants that for two years from the date of purchase of the Heat Alarm it will re pair or replace the Heat Alarm at the option of PSA Products Pty Ltd due to any manufacturing defect at the cost of PSA Products Pty Ltd excluding any labour costs ...

Page 8: ...et Burwood 3125 Victoria Australia Telephone 03 9888 9889 Facsimile 03 9888 9993 E mail enquiry psaproducts com au Website http www psaproducts com au AUSTRALIAN ELECTRICALAUTHORITY CS SGSE 100434 1004 7201 01 N10116 7 1004 7201 01 HA240 _V2 _ 2010 9 2 9 20 AM Page 8 ...

Reviews: