6. OPERATION, TESTING AND MAINTENANCE
6.3 Operating and Alarm Characteristics.
Function
LED Status
Sound emitted
Recommendation
Normal
Green ON
None
Green LED indicate the AC mains power is present.
Normal
Red FLASHING every 5
minutes.
None
Red LED flashes every 5 minutes is normal.
The smoke alarm performs a self test every 5 minutes.
The battery and electronics are tested for the life of the unit.
Local Alarm
Mode
Red light flashs. Smoke
alarm activated.
Repeat 3 long
beeps(ISO8201)
Indicate smoke alarm has activated and is in alarm mode.
The Red LED will be off after the alarm stops.
Interconnect
Alarm Mode
Red Light is OFF. Smoke
alarm activated.
Repeat 3 long
beeps(ISO8201).
Smoke alarm in full alarm, other interconnected units may
have activated the alarm. Check other smoke alarms or
devices.
Hush Mode
Red light flashing every 10
seconds.
None
HUSH button is pressed. Smoke alarm will silence
for approximately 9 minutes, After approximately
9 minutes will automatically exit hush mode.
Smoke Alarm
Memory
The red LED is pulsed
on three times every
40 seconds.
Pressing the button,
repeat chirp
Pressing the button, smoke alarm will chirp and red LED
pulse, and then upon release the button, the alarm memory
latch will be reset.
Low Battery
Flashing red light every
5 minutes.
Chirp every 40
seconds.
For LIF5800/2 model replace the battery.
For LIF5800RL/2 model, replace with new smoke alarm.
If the smoke alarm is initiating alarm, please reference 5.1.2.
Low Battery
Hush
Flashing red light every 5
minutes.
None
Pressing the hush button during low battery chirp will
silence the low battery chirp for up to 8 hours.
For LIF5800/2 model, replace the battery.
For LIF5800RL/2 model, replace with new smoke alarm.
If the smoke alarm is initiating alarm, please reference 5.1.2.
Chamber
Fault Mode
Flashing red light every 5
minutes.
Chirp 3 times
every 40 seconds
Clear alarm using a vacuum cleaner or compressed air,
if fault condition still exist after test, please replace with new
smoke alarm.