USAGE 

 

Function Differential thermostat

  

Monitors the temperatures in the tank and collector, controls output "R1 - circulation pump"  

 

   „Auto” mode 

 

Monitoring tº in the tank and collector  

 

When both [

tºcollector

 > 

tºtank 

dT + 2ºC]  and  

[

tºcollector 

>

T.CollectorStart

] are 

true,  the circulation pump is activated till  [

tºcollector

tºtank

 + 

dT - 2ºC

]  or tº colector 

falls below the T.CollectorStart. 

 

   „Vacantion” mode 
  

 

 

 

-

  During enough sunshine – it operates same way as in "Auto" mode  

-

  Activation of Circulation when [

tºcollector < tºtank  -10 ºC ] 

to cool the tank up to 

40 ºC

        

 

  Build in Protections: 

-

  Freezing  of  collector:  when  the 

tºcollector

  is  lower  than  T.collector  Defrost  -  2ºC,  the 

pump is  activated  to raise the 

tºcollector

 above T.collector  Defrost  +  2ºC,  but  only if the 

tºtank 

> 8ºC

  

-

  Overheating  of  the  tank:  when  the  [

tºtank   

>  T.Boiler  Max]  is  reached,  the  circulation  is 

disabled – unconditionally 

-

  Overheating  of  collector:  when  [

tºcollector

>

100  ºC

]  and  [

tºtank  <  T.BoilerMax]  are

 

reached, the pump is activated until

 tºcollector

 falls below 100 ºC

 

 

-

  High  temperature  (overheat  recovery):  When 

tºcollector

  reaches  a  range  of  110-140  ºC 

and 

tºtank

 <T. Boiler MAX, the circulation is activated at short intervals of 1 sec. every 20 

seconds - to slowly reduce the collector temperature. If 

tºcollector

 exceedes over 140°C, 

the circulation is strictly forbidden to protect the system from heat shock. 

-

  Pump blockage: automatic forced activation for 60 sec. every 7 days of inactivity

 

 

Monitors temperatures in the tank and controls the output "R2 - Heater" 

 

   „Auto”mode 

 

If tº tank < T.Boiler Thermostat , the output "R2 - Heater"

  

is

 

activated 

 

“Tank thermostat and Eco function is OFF”  

 “R2-Heater” output is activated once it is necessary. 

 

"Tank thermostat – and Eco function enabled"

 

  

Eco function: 

During enough sunshine and operation of the pump, the activation of the "R2 -Heater" 
output is postponed for 15 minutes after the last activation of the pump.  

 

„Vacantion” mode 

 

 

The 

"R2 - Heater"

 output is not activated except for frost protection

 

 

  Protection: 

of freezing of the tank: if 

tºtank

 goes

 

below 8°C, the "R2 -Heater" output is activated to 

heat up the tank  
 
 
 
 