ProVista Technology GTW1500HF Operation Manual Download Page 28

 28

device is functioning correctly. 

 

8.  Replacing the varistors 

The GTW1500 HF is a complex high-technology device. As a result, the possibilities for 
fixing faults on site are limited to just a few items. Please don't try to carry out repairs other 
than those described here. Use the ProVista’s service and repair service instead. 
 
If the red LED on the status display glows continuously during operation, you should 
first of all make sure that there is no earth fault in the PV generator 
 
1. Disconnect the GTW1500 HF from the low voltage grid (switch the line circuit breaker to 
its "off" position or pull out the AC plug). Make sure the grid cannot be 

inadvertently reconnected. 

 
2.

 

Disconnect the DC plug connectors for all 

3.

 

strings.    Make sure you note the order of the 

individual inverter inputs so you can put them back 
in the right place later! 
 
4.

 

Taking one DC plug connector at a time, 
measure 

  the voltages between one DC plug connector of a   

string and earth potential. Pay attention to the safety 
warnings! 

 
 
 
 

Warning

 

 

Dangerous high voltages may be present. Danger of death! 

 

5. the measured voltages are constant and if their total is roughly the same as the open circuit 
voltage of the string then there is a earth fault in this string. Its approximate location can be 
deduced from the relationships between the voltages 
6. Repeat points 3 and 4 for each string 
If you found a earth fault, it is probably not necessary to replace the varistors. Instead, make 
sure the ground fault is fixed. Generally the PV generator's installation  engineer  should  
be  hired  for  this  job.  In  this  case  continue  as described under point 10, but 
without reconnecting the faulty string. Protect its DC plug against accidental touch contact 
(e.g. by fitting the protective caps or using sufficient high-voltage insulating tape). 
If you did not find any earth fault in the PV generators, it is likely that one of the thermally 
monitored varistors has lost its protective function. These components are wearing parts. 

Summary of Contents for GTW1500HF

Page 1: ...GTW1500HF Grid Inverter Operation Manual...

Page 2: ...arranty or liability claims for all kinds are excluded in case of damages due to Inappropriate use of the product Operation of the product in an improper environment Operation of the product without c...

Page 3: ...ct Please read these sections carefully in order to avoid any damages of the equipment and for optimal personal protection Note This symbol indicates information that is required for the optimal opera...

Page 4: ...ace 13 4 3 4 Auto test display interface 14 5 Installation requirements 17 5 1 Installation requirements 17 5 1 1 Ambient conditions 17 5 2 Position 18 5 3 Installation 18 6 Electrical connection 20 6...

Page 5: ...The GTW1500 HF is equipped with the ProVista grid guard This is a type of independent disconnection device It ensures that the GTW1500 HF complies with the IEC AS regulations for the connection and p...

Page 6: ...electrician Hazardous and even lethal voltages can be encountered within the enclosure Before working on the GTW1500 HF with the lid removed the AC and DC voltages MUST be disconnected from the GTW15...

Page 7: ...minute Beware of hot surface The inverter can become hot during operation Avoid contact during operation Caution risk of danger Observe all documentation that accompanies the inverter The inverter mu...

Page 8: ...tem consists of PV arrays photovoltaic combiner box photovoltaic grid connected inverter metering devices and utility grid see figure 3 1 Figure 3 1 PV Grid connected system Note Need permission from...

Page 9: ...ogy for maximum power point tracking MPPT 99 MPPT efficiency Wide input voltage range Efficient design of high frequency isolation transformer High efficiency at wide power range Advanced anti islandi...

Page 10: ...rning if sufficient insolation is available and therefore if a certain minimum voltage is present in the inverter If as nightfall approaches the voltage drops below the minimum voltage value gird fee...

Page 11: ...f inverter from these lights The states of each LED light signals are in the following table LED Color Status Green RUN means normal operation Yellow STARTING means start operation Red ALARM means ove...

Page 12: ...go into the Checking LCD screen display as Menu 3 it also shows another if the progress is updated Menu 3 Checking Yellow LED display Checking 4 3 2 Operating parameters display interface About 2 sec...

Page 13: ...7 display interface Menu 9 to Menu 15 it also shows another if the progress is updated Menu 9 RED LED display PV Array Voltage Out of range Menu 10 RED LED display DC Component Out of range Menu 11 RE...

Page 14: ..._Grid Inverter Display Ver 1 10 Control Ver 1 10 Please beat the panel Auto Test Please beat the panel Auto Test Start Grid Volt High Protection 261V Grid Volt High Protec Max 262V Grid Volt High Prot...

Page 15: ...High Protection 51 0Hz Grid Freq High Protection 50 9Hz Grid Volt Low Protection 187V Grid Volt Low Protection 188V Grid Volt Low Protection 230V Grid Volt Low Prote Pass 230V Grid Volt Low Protec Mi...

Page 16: ...Low Prote Pass 50 1Hz Grid Freq Low Prote Time 40ms Test Finish Grid Freq Low Prote Min49 0Hz Grid Freq Low Protection 49 0Hz Grid Freq Low Protection 49 1Hz Grid Freq Low Protection 50 1Hz Grid Freq...

Page 17: ...The GTW1500 HF should be installed in a place where it is not exposed to direct sunlight An increased ambient temperature can reduce the yield of the PV system Provide better ventilation for GTW1500 H...

Page 18: ...sides 40cm In front 40cn 5 2 Position The GTW1500 HF is designed to be mounted on a vertical wall For an optimum energy yield and the most convenient operation vertical installation at eye level is p...

Page 19: ...stallation position The space between every every holes is shown as below photo Keep drilling vertical to the wall and don t shake the drill to avoid holes tilting 2 Please fix the wall bracket on the...

Page 20: ...ecifications Before installation please reference the wires recommended sizes as below table Wire Requirements AWG PV DC wire 12AWG PV DC wire 12AWG GND wire 12AWG Grid L wire 12AWG Grid N wire 12AWG...

Page 21: ...diameter between 7mm and 12mm as below photo showing 4 Connect the individual conductors into the socket s terminals with correct polarity and position as below photo showing and make sure the wires a...

Page 22: ...ocket is fully assembled 6 3 PV connection steps Warning Make sure the PV array to be negative grounding The PV generator strings are connected directly to the terminal in the connection box Connect t...

Page 23: ...sure that no voltage is present at the cable Connection procedure 1 Parts of the positive plug 2 Proceed the cable as below photo showing 3 Connect the positive pin and rivet line together as below p...

Page 24: ...o showing insert the cable with riveting pin pic2 into the main unit it is appropriate when you hear the sound after inserting please have a anti pull to double check if matched firmly 7 As the below...

Page 25: ...he input side of inverter add an AC circuit breaker at the output side of inverter And the requirement models of breakers as table Breakers Requirement model DC Breaker 600VDC 16A AC Breaker 400VAC 10...

Page 26: ...he maximum string voltage of 400 V DC Warning If the voltage of the PV modules the maximum input voltage of the inverter it can be destroyed by the overvoltage This will void all warranty claims Do no...

Page 27: ...mation page 6 7 1 Opening the GTW1500 HF Follow the sequence below under all circumstances 1 Switch the line circuit breaker to the off position 2 Disconnect the PV generator from the GTW1500 HF 3 Wai...

Page 28: ...the voltages between one DC plug connector of a string and earth potential Pay attention to the safety warnings Warning Dangerous high voltages may be present Danger of death 5 the measured voltages...

Page 29: ...tors that affect all varistors in a similar way temperature age inductive overvoltages it is highly recommended that you replace both varistors not just the one that is obviously defective The varisto...

Page 30: ...ltage Uac 200 260 V AC Nominal grid frequency 50Hz Operating range grid frequency f 49 51 Hz AU 47 5 50 2Hz Germany Total Harmonic Distortion 5 to Standard EMI compliant with CE AS4777 Standard All po...

Page 31: ...r GTW1500 HF without express authorization and instructions 10 Contact In the case of complaints or faults we request that you contact the local supplier from whom you got this product installed They...

Page 32: ...32 11 Appendix A Model Number Conversion Table Descriptions Model Number For Protronic use Model Name For provista use 1500W Grid Connected inverter SGA015 GTW1500HF...

Reviews: