Proton Guard G710 Operation Manual Download Page 24

24

Однофазный трехскоростной

АС-двигатель

Однофазный трехскоростной

АС-двигатель

Однофазный трехскоростной

АС-двигатель

13. WIRING PROTON G 710

13.2 Wiring  of  single-phase  three-speed  AC-motor  to  switch  panel 

RS 330 and thermostat RA (RT 55, RD)

13.3

Single-phase three-speed

AC-motor 

Single-phase three-speed

AC-motor 

RTS 10

HEAT
OFF
COOL

HIGH
MED
LOW

9 8 7 6

1 2 3 4 5

N

PE LO

HI

ME

N

SRV

N

SRV

L N PE

B

4

V

V

N

PE LO

HI

ME

230

 V/50

 Hz

Wiring  of  single-phase  three-speed  AC-motors  to  the  switch 

panel  RTS 10  (having  reached  set  temperature  in  a  room  the 

valve SRV closes)

Provide  installation  of  a  device  protecting 

the  motor  from  shunt  fault  (B  on  the 

scheme).

4

Summary of Contents for Guard G710

Page 1: ...NS MANUAL FOR AIR HEATER PROTON GUARD Safety precautions Technical parameters Installation Construction and dimensions www protongroup org PROTON GUARD RU EN Air heater with corrosion resistant heat e...

Page 2: ...t medium 3 4 5 4 Dimensions 6 5 Construction 7 6 Technical characteristics 8 13 9 14 7 Mounting consoles 8 Installation 10 Maintenance 15 11 Operational conditions 16 12 Control elements 12 1 Control...

Page 3: ...ior notification The manufacturer preserves the right to alter the construction which doesn t impact its functioning and basic technical parameters The air heater is intended only and exclusively to b...

Page 4: ...of joints before filling in the heat medium Installation and connection of the equipment to pipelines and networks must be performed by qualified personnel only having appropriate access During insta...

Page 5: ...ely heavy conditions increased dustiness aggressive particles in the air corrosiveness Design solutions applied in this series significantly increase operational safety and life time Due to using casi...

Page 6: ...4 DIMENSIONS Dimensions of the air heater PROTON GUARD 6 580 675 350 675 Dimensions of the air heater PROTON GUARD with the front panel and louvers Depends on a motor type 680 680 390 590...

Page 7: ...in the shape of a ring around fan blades as well as creates a body of the air heater Fans applied are axial and can have either single phase electronically commutated or single phase asynchronous mot...

Page 8: ...4 26 8 20 9 11 1 15 7 23 8 18 2 13 3 6 TECHNICAL CHARACTERISTICS General parameters Number of heat exchanger rows Airflow Heating power Air temperature increase Max temperature of heat medium Max wor...

Page 9: ...of installation Fasten the mounting console on the air heater s body using fixing screws and rings 1 2 3 Use fasteners designed for the material which the base is made of 7 MOUNTING CONSOLES 7 1 Insta...

Page 10: ...les Noncompliance with the minimal distance 0 25 m from a wall or ceiling will lead to wrong operation of the air heater which in turn will influence the useful life of the equipment On a wall vertica...

Page 11: ...e console under necessary angle position using anchoring screws are to be bought separately 3 Install the air heater on the console in the position into the hole on the console position Then putting t...

Page 12: ...n a wall with bend to the right or left under angle 0 to 90 Noncompliance with the minimal distance 0 25 m from a wall or ceiling will lead to wrong operation of the air heater which in turn will infl...

Page 13: ...0 25 m 4 12 m directing louvers are installed under angle of 45 directing louvers are installed vertically directing louvers are installed symmetrically under angle of 45 8 INSTALLATION Noncompliance...

Page 14: ...e inlet and outlet pipes 1 2 It is recommended to install a coarse filter on the inlet pipe 3 Provide at least one cock for heat medium drainage on the bottom point on the piping scheme of the air hea...

Page 15: ...on its lamellas lowers heating output of the air heater as well as negatively influences fan functioning creating extra aerodynamic resistance Clean the heat exchanger following these steps Be careful...

Page 16: ...d 5 Concentration Chemical strength Excellent Good 10 20 30 Sulfuric acid 5 10 20 30 Phosphoric acid 5 10 20 30 50 Acetic acid Trichloroethylene Ethyl alcohol Toluene 10 16 Operational conditions 11 O...

Page 17: ...temperature and regulate heat medium supply by a valve s drive The thermostat with IP55 can be installed in various buildings including dusty and humid environments Accurate measurement due to capill...

Page 18: ...ary temperature Energy savings Ability to regulate the motor Easy to operate Comfortable temperature control with accuracy of up to 1 C Reduction of the noise level POWER BOX ontrol device POWER BOX i...

Page 19: ...at supply system A valve with actuator power supply 230 V allows to regulate heat medium supply in a standalone mode from a controller or thermostat More information about ECOMATIC PRO you can receive...

Page 20: ...ted control over EC motor speed Control signal 0 10V Ability to connect one or a few external thermal sensors PT 1000 Wide range of settings and flexible control Avoidance of influence of human factor...

Page 21: ...system A valve with actuator power supply 230 V allows to regulate heat medium supply in a standalone mode from a controller or thermostat SRV Two way valve with actuator The hub is a box which combi...

Page 22: ...Hz L N PE B4 RS 330 LO L HI ME 1 N PE LO HI ME Provide installation of a device protecting the motor from shunt fault B on the scheme 4 Single phase three speed AC motor Single phase three speed AC mo...

Page 23: ...L HI ME 1 N PE LO HI ME 230 V 50 Hz L N PE B4 N SRV V RA RD NTC65 RT 55 V L V L or or 1 PE 2 V L 11 10 9 8 7 6 5 Wiring of single phase three speed AC motor to switch panel RS 330 and thermostat RA R...

Page 24: ...HIGH MED LOW 9 8 7 6 1 2 3 4 5 N PE LO HI ME N SRV N SRV L N PE B4 V V N PE LO HI ME 230 V 50 Hz Wiring of single phase three speed AC motors to the switch panel RTS 10 having reached set temperature...

Page 25: ...OFF COOL HIGH MED LOW 9 8 7 6 1 2 3 4 5 N PE LO HI ME L N PE B4 N PE LO HI ME 230 V 50 Hz Wiring of single phase three speed AC motors to the switch panel RTS 10 having reached set temperature in a r...

Page 26: ...peed AC motor N SRV V N PE LO HI ME N SRV RTS 30 1 2 3 4 5 6 7 8 9 NTC 65 10 11 L N PE B4 V N PE LO HI ME 230 V 50 Hz Wiring of single phase three speed AC motors to programmable ontroller RTS 30 Prov...

Page 27: ...to one line N PE LO HI ME N SRV V N PE LO HI ME N SRV V POWER BOX 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 LO PE N V ME HI 7 6 5 4 3 2 1 230 V 50 Hz L N PE B4 N SRV V N PE LO HI ME Up to 9 air heaters can...

Page 28: ...ED LOW 9 8 7 6 1 2 3 4 5 N PE LO HI ME Up to 3 air heaters can be connected to one line Provide installation of a device protecting the motor from shunt fault B on the scheme 4 230 V 50 Hz Wiring of s...

Page 29: ...Single phase three speed AC motor Single phase three speed AC motor Single phase three speed AC motor SRV SRV SRV Wiring of single phase three speed AC motors to POWER BOX with programmable ontroller...

Page 30: ...SRV SRV SRV Wiring of single phase three speed AC motors to POWER BOX with programmable ontroller RTS 30 connection of fans to different wires Single phase three speed AC motor Single phase three spe...

Page 31: ...ow GND 14 1 230 V 50 Hz L N PE B 4 PM 10 It is necessary to provide motor protection from overheat so wire the contacts TK to a device which controls power Use shielded wires in the control cable Wiri...

Page 32: ...sor PT 1000 must be installed in a representative point You should avoid places directly exposed to solar radiation electromagnetic waves etc Electronically commutated EC motor Electronically commutat...

Page 33: ...y exposed to solar radiation electromagnetic waves etc Use shielded wires in the control cable Electronically commutated EC motor Electronically commutated EC motor ECP 510 TK TK PE N L Tach V cc 1 V...

Page 34: ...5 59 4 75 9 95 7 118 8 145 2 171 6 11 6 15 1 19 8 25 7 36 3 46 2 56 1 72 6 92 4 112 2 132 0 4 4 6 1 7 9 13 2 18 7 29 7 50 6 36 3 22 0 44 0 11 0 19 0 27 0 38 0 46 0 70 0 85 0 115 0 135 0 175 0 215 0 2...

Page 35: ...onsumption Inside diameter Type 15 kW 23 kW 39 kW 61 kW 96 kW 180 kW 20 mm 25 mm 32 mm 40 mm 50 mm 70 mm 3 4 1 11 4 1 2 2 0 6 m h 1 0 m h 1 6 m h 2 5 m h 4 0 m h 8 0 m h 1 2 1 2 15 REFERENCE INFORMATI...

Page 36: ...vice proton kiev ua www protongroup org www protongroup org In case of any failures in operation of equipment address the authorized support centers of the Manufacturer For information about support c...

Reviews: