Exhaust connections:
- If the exhaust is located within 1.80 of the ground, you must install an end protection kit.
- The openings of a terminator for separate pipes must come out within a 50cm square.
Horizontal exhaust system Ø 60/100 mm (type C13)
Horizontal exhaust system Ø 80/125 mm (type C13)
L
63
1
1 Joint
Type
Max length
Ø 60/100
10m
Ø 80/125
12m
Vertical exhaust system Ø 60/100mm or Ø 80/125mm (type C33)
Type
Max length
Ø 60/100
10m
Ø 80/125
13m
Each time an extra 90° elbow is needed (or 2 at 45°),
the length (L) must be reduced by 1m.
L
1
L
Each time an extra 90° elbow is needed (or 2 at 45°),
the length (L) must be reduced by 1m.