AC-200-dual USER MANUAL V2.30

13/14

Main troubleshooting

Malfunction

Reasons

Solution

Low vacuum degree

1. Insufficient vacuum pump oil.
2. Pump oil emulsion, dirty
3. Pump oil inlet plugged.
4. Leakage in pump connection.
5. Components worn out.

1. Add oil to central line
2. Put new oil
3. Clean oil inlet.
4. Check connection
5. Maintain the machine, especially o-ring,
washer and other sealing parts.

Vacuum pump inject
oil.

1. Excessive oil volume.
2. Entrance pressure too high.

1.Discharge some oil to proper level
2.Run Recovery function first.

No display

1. Fused (in Power cable connection
box, or PCA)
2. PCA burnt.
3. Power cable loosened.
4. LCD not work

1. Change fuses.
2. Change PCA.
3. Connect power cable reliably.
4. Change LCD.

Recovery does not
stop

1. Leakage in automotive A/C or

equipment pipeline.

2. Compressor not work
3.Pressure sensor does not work

Remarks: In winter, it is normal
that recovery takes longer time.

1. Make leakage test. Machine leakage test

with referenc to service manual.

2. Change compressor.
3. Fasten pressure sensor connection to

PCA, or change the pressure sensor.

No change in
recovery volume

1. No refrigerant in A/C.
2. Support screw of gas cylinder load
cell not loosened.
3.Gas cylinder load cell not work or
PCA failure

1. Stop recovery.
2. Unsrew the protection screw, as chapter

“Operation preparations”.

3. Calibrate gas cylinder load cell, or change

the load cell, or change PCA.

While auto A/C has
refrigerant,
equipment displays
alarm 005

Low pressure switch plug

disconnected from PCA socket.

Fasten low pressure switch plug.

High pressure alarm
004 but gas cylinder
gauge does not show
excessive pressure
value

1. High pressure switch plug
disconnected from PCA socket.
2. Pipeline connecting compressor
exit blocked.

1. Fasten high pressure switch plug.
2. Inspect the hoses and connections between
compressor exit and tank blue hand vale.

No charge or slow
charge.

1.Insufficient refrigerant in
equipment
2.Charge line problem.

1. Fill equipment tank with more refrigerant.
2..Check charge line, including tank red

valve, tank red hose, solenoid #5, solenoid
#9 (high side), solenoid #11 (long side),
service hoses and HP/LP quick couplers.

Summary of Contents for AC-200-dual

Page 1: ...PROTEC AC 200 dual USER MANUAL AC 200 dual USER MANUAL...

Page 2: ...still highly recommended to leave maintenance job to specialized technicians self troubleshooting and convenient USB upgrade etc General safety The storage cylinder in this unit contains liquid refrig...

Page 3: ...TABLE 3 PART DESCRIPTION 4 OPERATION PREPARATIONS 5 EQUIPMENT CONNECTION Recovery vacuum oil injection charge Tank fill auto mode 7 RECOVERY 8 VACUUM 8 OIL INJECTION 9 CHARGE 9 TANK FILL 9 AUTO MODE 1...

Page 4: ...of dual gas cylinders one for R 134a one for HFO 1234yf 10KG New oil bottle capacity 250ml Used oil bottle capacity 400ml Dual condensers and cooling fans one for R 134a one for HFO 1234yf Max Pressu...

Page 5: ...A C system Tank fill Transfer liquid refrigerant from an external refrigerant storage cylinder to equipment cylinder Auto mode Performs the selected functions in a fully automatic sequence The machine...

Page 6: ...ad LP gauge R134a HFO1234yf Coupler connect fittings LCD screen HP gauge Fuse Power switch Vacuum pump New oil vessel Used oil vessel R134a refrigerant tank HFO1234yf Refrigerant tank R134a tank gauge...

Page 7: ...2 When you need transport the machine please screw those bolts on Fill equipment with refrigerant New equipment is empty you need to fill the equipment with refrigerant and refrigeration oil Through t...

Page 8: ...select refrigerant type If the refrigerant type selected is different from the refrigerant handled at previous operation the machine automatically recovers refrigerant inside machine pipelines and ma...

Page 9: ...ment Connection For recovery vacuum oil injection charge Auto Mode Warning Except the situations clearly stated in the manual during all equipment operations please maintain the vehicle engine and A C...

Page 10: ...internal refrigerant cylinder The machine should be left connected on the vehicle for a minimum time of 3 minutes longer in cold climates for any pressure increase test If after 3 minutes or longer if...

Page 11: ...s ENTER to start the process You can manually set charge amount with volume or select Charge by database to set charge amount by car make and model You can choose to charge through high side low side...

Page 12: ...to do calibration of load cells The load cell calibration is very simple and fast with just one step 1kg weight calibration step Warning Misoperation in calibration could bring about serious conseque...

Page 13: ...message Click OpenFile to select update to update e g file AC200 DUAL_V2 01 for main program update or Database_V2 02 for database update Then click Connect the PC displays the following message Clic...

Page 14: ...re next maintenance is displayed in the left beneath part of each operation interface Upon 480 operations having been made the machine displays the following message and users can continue using the e...

Page 15: ...to service manual 2 Change compressor 3 Fasten pressure sensor connection to PCA or change the pressure sensor No change in recovery volume 1 No refrigerant in A C 2 Support screw of gas cylinder loa...

Page 16: ...ve base is not well sealed Remove solenoid 8 from valve base clean the solenoid valve and valve base During vacuum there is suction in old oil bottle The contact between solenoid valve 2 and valve bas...

Reviews: