PAGE 50
APPENDIX A
– PROGRAMMABLE FEATURES
12. APPENDIX A
– PROGRAMMABLE FEATURES
Alarm Messages
Unique Site ID plus individual messages for each input. Message length is variable
Alarm Polarity
Selects NO or NC input format
Alarm Latch
Latches fleeting alarm inputs
Alarm Debounce
Selects the delay time before a change of state on the input is valid. Range is 0.1 to
19.9 in either seconds or minutes
Alarm Directory
Selects one of four directories that contain command actions to be taken when the
alarm is active.
Interval Timer
Two stage timer that uses ‘A’ interval ‘A’ times before switching to ‘B’ interval.
Both ‘A’ and ‘B’ interval are adjustable up to 249 minutes.
Acknowledge Code
Stops the reporting sequence: 1 to 8 digits
Interrogate Code
Speaks alarms and relay state: 1 to 8 digits
Alarm On/Off Output Codes Sent when an alarm becomes active (on) or when it returns to normal (off). Different
codes for each alarm. 1 to 8 digits
Remote Alarm Input
Simulate an alarm condition when received. Different codes for each alarm. 1 to 8
digits
Directory Control Code
Changes the alarms to use different directories; also referred to as shift change.
Two modes are available: one where all alarms are assigned to Directory A and can
be controlled to alternately use the other three directories and another where
Directory A alternates with Directory B and Directory C alternates with Directory D.
Directory Commands
Each directory can have up to 20 lines of command sequences. The commands are
executed when an alarm using the directory is active. The commands are:
Dial - phone the programmed number.
Voice - Speak the alarm messages
Radio - turn on the radio transmitter
Wait - Insert a pause: 1 to 249 seconds.
2 Tone - send a two tone page
5 Tone - send a five tone page
1 Tone - send a single tone
Alert - send a beeping tone
DTMF - send a string of digits
Answer - monitor the call progress signals and wait for the called party to
speak before announcing the alarm message.
Access Code
Password for dial-up access to programming:1 to 8 digits
Acknowledge Request
The acknowledge request at the end of the alarm annunciation can be disabled for
use with public address systems.
Number of Rings
Sets the number of rings before the B1290 will answer the line: 1 to 8 rings or never.
Squelch Polarity
Sets the radio busy monitor to either high or low when busy.
Relay Voices
Voice messages that are returned when a relay is operated.
Disable Relay Voices
Relay voices are not spoken.
Relay On/Off Codes
DTMF codes that turn the relay on and off. Independent for each relay: 1 to 8 digits
Relay Timer
Makes the relay a timed type where it will remain on for the specified time after the
On code is received. Range is 1 to 199 in either seconds or minutes
Relay Special Function
These automatic functions can be assigned to the relays:
Relay 1: New (unacked) alarm on
Relay 2: Any alarm on
Relay 3: Alarm acknowledged (timed)
Relay 4: Error
Summary of Contents for Plus B1290
Page 1: ...Installation Operation Manual January 2022 Rev 2 04 ...
Page 4: ......
Page 19: ...OPERATION PAGE 15 ...
Page 49: ...PROGRAMMING EXAMPLES PAGE 45 etc ...
Page 60: ...PAGE 56 APPENDIX C PROGRAMMMING TREE Next ...
Page 61: ...APPENDIX D MOUNTING PAGE 57 15 APPENDIX D MOUNTING Figure 9 Mounting Detail ...