![ProSoft Technology ProLinx ASCII Driver Manual Download Page 25](http://html1.mh-extra.com/html/prosoft-technology/prolinx-ascii/prolinx-ascii_driver-manual_1618953025.webp)
Driver Status Data
ASCII
♦
ProLinx Standalone
Generic ASCII Serial Communication Module
ProSoft Technology, Inc.
Page 25 of 40
July 7, 2008
5 Driver
Status
Data
Each ASCII port associated with the ASCII driver has an associated status data
area. This data is located in the virtual address range of the module. The map
data functionality of the module must be used to map this data into the normal
data range of the module's database. The following table lists the content of the
status data areas associated with each ASCII port driver:
Port 0 Status Data
Status Register
Description
13000 Receive
State:
-1 = Listening for data
1 = Receiving Port Data
2 = Waiting for Backplane transfer
13001
Receive character count
13002
Receive message count
13003 Transmit
State:
0 = Waiting for Data to Send
1 = RTS On
2 = RTS Timeout
3 = Sending data
4 = Waiting for RTS Off
5 = RTS turned off
30 = Intercharacter Delay
31 = Intercharacter Delay
32 = Intercharacter Delay
100 = Message Delay before Transmit
101 = Message Delay before Transmit
13004
Transmit character count
13005
Transmit message count
13006 Configuration
error
word
13007 to 13009
No Valid Data
Port 1 Status Data
Status Register
Description
13010 Receive
State:
-1 = Listening for data
1 = Receiving Port Data
2 = Waiting for Backplane transfer
13011
Receive character count
13012
Receive message count