PLX51-PBM
Setup
PROFIBUS DPV0/DPV1 Master or Slave to EtherNet/IP™ or Modbus® Gateway
User Manual
ProSoft Technology, Inc.
Page 25 of 196
3.5
PLX51-PBM Parameters
The PLX51-PBM parameters will be configured by the PLX50 Configuration Utility.
Refer to the additional information section for documentation and installation links for
ProSoft Technology
’s PLX50 Configuration Utility.
3.5.1
General
The General configuration is shown in the figure below. The PLX51-PBM General
configuration window is opened by either double clicking on the module in the tree or
right-clicking the module and selecting
Configuration
.
Figure 3.19
– PLX51-PBM General configuration
The General configuration consists of the following parameters:
Table 3.1 - General configuration parameters
Parameter
Description
Instance Name
This parameter is a user defined name to identify between various PLX51-
PBM modules.
Description
This parameter is used to provide a more detail description of the application
for the module.
IP Address
The IP address of the module.
Mode
The PLX51-PBM can operate in one of three modes:
Quiet
This mode allows the user to connect the PLX51-PBM to an active bus and
run a DP packet capture. In this mode the PLX51-PBM will not communicate
on the DP Bus but rather only listen.
Standalone Master
In this mode the PLX51-PBM is the DP Master on the PROFIBUS network.
Slave
In this mode the PLX51-PBM will emulate multiple PROFIBUS Slave
devices.
Primary Interface
This is the network the PLX51-PBM will interface the PROFIBUS network.
EtherNet/IP (Logix)