
Diagnostics and Troubleshooting
MVI69E-MBTCP ♦ CompactLogix Platform
User Manual
Modbus TCP/IP Enhanced Communication Module
Page 94 of 150
ProSoft Technology, Inc.
June 28, 2017
6.2
LED Status Indicators
ETH
CFG
CLT
BP
SRV
OK
The LEDs indicate the module’s operating status.
LED
Color
Indication
ETH
Green
Application is running and Ethernet is ready
Off
Application is not running
CLT
Red
Exception response received from the server; bad address,
command, etc
SRV
Red
Exception message received from the client
CFG
Red
Error in configuration
Green
Configuration is OK
Amber
Configuration state
Off
Application is not running or backplane has failed
BP
Red
Processor is not in RUN mode
Green
(Flashing) BP transfer is operational
Amber
Initialization state
Off
Application is not running
OK
Red
Application is not running
Green
Application is running
During module configuration, the OK LED is red and the BP LED is on. If the BP
ACT and OK LEDs blink at a rate of every one-second, this indicates a serious
problem with the module. Call ProSoft Technology Technical Support to arrange
for repairs.
6.2.1 Clearing a Fault Condition
Typically, if the OK LED on the front of the module remains RED for more than
ten seconds, a hardware problem has been detected in the module or the
program has exited.
To clear the condition, follow these steps:
1
Turn off power to the rack.
2
Remove the card from the rack.
3
Verify that all jumpers are set correctly.
4
If the module requires a Compact Flash card, verify that the card is installed
correctly.
5
Re-insert the card in the rack and turn the power back on.
6
Verify correct configuration data is being transferred to the module from the
CompactLogix controller.
Summary of Contents for MVI69E-MBTCP
Page 4: ......