1.7 Hardware Specifications
General
Specification
Description
Backplane Current Load
800 mA @ 5 V DC
3 mA @ 24V DC
Operating Temperature
0° to 60°C (32 to 140°F) - MN/I56E-MCM
-25° to 70°C (-13° to 158°F) - MVI56E-MCMXT
Storage Temperature
-40° to 85°C (-40 to 185°F)
Extreme/Harsh Environment
MVI56E-MCMXT comes with conformal coating
Shock
30g Operational
50g non-operational
Vibration: 5 g from 10 to 150 Hz
Relative Humidity
5% to 95% (non-condensing)
LED Indicators
Battery Status (ERR)
Application Status (APP)
Module Status (OK)
4-Character, Scrolling, Alpha-Numeric
LED Display
Shows Module, Version, IP, Port Master/Slave
Setting, Port Status, and Error Information
Debug/Configuration Ethernet port (E1 - Config)
Ethernet Port
10/100 Base-T, RJ45 Connector, for CAT5 cable
Link and Activity LED indicators
Auto-crossover cable detection
Serial Application ports (P1 & P2)
Full hardware handshaking control, providing radio, modem, and multi-drop support
Software configurable communication
parameters
Baud rate: 110 baud to 115.2 kbps
RS-232, 485 and 422
Parity: none, odd or even
Data bits: 5, 6, 7, or 8
Stop bits: 1 or 2
RTS on/off delay: 0 to 65535 milliseconds
App Ports (P1, P2)
RJ45 (DB-9M with supplied adapter cable)
Configurable RS-232 hardware handshaking
500V Optical isolation from backplane
RS-232, RS-422, RS-485 jumper-select, each port
RX (Receive) and TX (Transmit) LEDs, each port
Shipped with Unit
RJ45 to DB-9M cables for each serial port
5 foot Ethernet Straight-Thru Cable (Gray)