Configuring the Module with RS Logix 500
MVI46-PDPS
♦
SLC Platform
Profibus DP Slave Communication Module
ProSoft Technology, Inc.
Page 27 of 72
April 30, 2008
Note: Although valid PROFIBUS Node addresses range from 0 to 125, Node 0 is not a valid node
number for a Slave module and that Nodes 0, 1, and 2 are usually reserved for PROFIBUS
Masters. Users are advised to use Node numbers 3-125
2.6.2 Swap Input Bytes
Yes or No
This parameter specifies if the data in the input data area of the module is to be
byte swapped. If the order of the bytes in the words stored in the database is not
correct, use this option. A value of Yes causes the module's program to swap the
bytes in each word. A value of No indicates no byte swapping will occur.
2.6.3 Swap Output Bytes
Yes or No
This parameter specifies if the data in the output data area of the module is to be
byte swapped. If the order of the bytes in the words stored in the database is not
correct, use this option. A value of Yes causes the module's program to swap the
bytes in each word. A value of No indicates no byte swapping will occur.
2.6.4 Comm
Failure
Mode
0 or 1
This parameter sets the data transfer mode of the module's PROFIBUS output
image to the internal database when a communication failure on the PROFIBUS
interface is detected. If the parameter is set to 0, the output image will continue to
be transferred. If the parameter is set to 1, the output image will not be
transferred and the last values will be retained.
2.6.5 Comm
Timeout
Multiplier
1 to 10
This parameter sets the communication timeout value for the module. The value
entered is multiplied by 125 milliseconds to determine the actual timeout value.
For example, a value of 1 specifies a communication timeout of 125 milliseconds.
2.7 Download
the
Project to the Module
In order for the module to use the settings you configured, you must download
(copy) the updated Project file from your PC to the module.
To Download the Project File
1
In the tree view in ProSoft Configuration Builder, click once to select the
MVI46-PDPS module.