ILX34-AENWG
♦
POINT I/O Platform
Procedures
Wireless Point I/O Adapter
Setup Guide
Page 36 of 79
ProSoft Technology, Inc.
July 31, 2009
3
In the
M
ODULE
P
ROPERTIES
dialog, enter the following information:
a) Name
b) Slot
In the
M
ODULE
D
EFINITION
area of the dialog box, notice that the default
Connection type is
R
ACK
O
PTIMIZATION
.
4
Click the
C
ONNECTION
tab, and then change the RPI value for the module
from 20 (the default) to 10 (the recommended value for digital modules). This
value determines how often to exchange data with the ILX34-AENWG
adapter.
Important
: To avoid overloading the ILX34-AENWG adapter, we recommend that RPI be no less
than 10 ms for rack connections and 50 ms for direct connections.