• The control unit must receive 115V AC +/- 5% and 60 Hz from the AC outlet.

• These primary pumps will not provide protection during a power outage. With the

risk of property damage from high water levels, the addition of a Pro Series battery
backup sump pump system is highly recommended.

• After the initial installation, be sure to check the operation by filling the sump

with water and observing the pump operation through one full cycle.

• For continuous duty operation, the pump must be submerged at least 3/4 of the

depth of the pump at all times.

• In instances where the discharge line is exposed to freezing temperatures, the pipe

must be sloped downward so any remaining water will drain out. Failure to do so
will prevent water from exiting the sump and damage the pump if the line freezes.

Installation Instructions

Prior to Installation

1. Visually inspect your pump. Products may be damaged during shipping. If the

product has been damaged, contact your place of purchase or Glentronics, Inc.
before installation.

2. Thoroughly read the instructions provided to learn specific details regarding

installation and use. This manual should be retained for future reference.

1. Use a pit that conforms to all local

codes and is large enough to
accommodate the pump and float
switch. The minimum requirements for
the 1/3 HP pump with the double
float assembly are 8

in diameter and

14

deep, for the 1/2 HP pump they

are 10" in diameter and 16" deep.

However, larger sump pits are
preferred, since they will extend the
discharge cycle and reduce the
number of times the pump turns on.

2. Clean the pit of all debris. The

pump’s strainer must be kept clear.

3. The pump should not be set directly

onto a clay, earthen, or sand base.
You may install bricks or blocks under
the pump to provide a solid base.

4. The pump should be level.

5. Install discharge plumbing according

to local, regional and state codes.
Rigid PVC pipe is recommended.

6. An in-line check valve is

recommended to prevent back-flow.
This check valve is mandatory when sharing a discharge line with another pump
(i.e. a back-up pump or a second primary pump).

7. Install a gate valve or ball valve if required by any codes.

8. The pipe must be positioned in a downward slope so any remaining water will drain

away. Failure to do this will prevent water from exiting the pit and damage the
pump if the line freezes.

9. If you are replacing an old sump pump:

(a) Unplug the pump from the outlet.

(b) Loosen the check valve or rubber union by

unscrewing the bottom hose clamp. (If the
existing system is installed without a check
valve or rubber union, saw the pipe apart above
the sump pit.)

(c) Remove the old pump and unscrew the pipe and

adapter.

(d) If the adapter fits into the new pump, screw the pipe into the pump. If not, cut

a piece of rigid PVC pipe and connect it to the new adapter by cleaning and
cementing the two pieces together. (Follow the instructions on the PVC cleaner
and cement.)

(e) Loosen the enclosed stainless steel hose clamp by turning the screw

counterclockwise and slip it over the pipe on top of the pump.

(f) Hold the float switch against the discharge pipe so the cage is below the bracket.

(g) Position the bottom of the float at the height you want the pump to activate and

turn the screw clockwise to tighten the hose clamp, but do not tighten it
completely at this time.

(h) Lower the pump into the sump by the handle.

(i) To avoid debris pouring into the float, it should be positioned on the side of the

discharge pipe opposite the drain tile. Note: It is desirable to mount the float
below the drain tile that empties into the pit. Mounting it above the drain tile
would allow water to fill the drain tile before the pump is activated. (See diagram).

(j) Once the switch is in the desired position, tighten the hose clamp.

(k) Connect the pipe on the pump to the existing discharge pipe with a rubber union

or check valve and tighten the hose clamps securely.

Connecting the Pump and Controller

Dual Float Controller

Plug the control box into a properly
grounded, 3-prong receptacle (preferably
with ground fault circuit interrupt), then
insert the pump plug into the receptacle
on the control box. You should provide
additional protection for the control unit
by using a surge protector.

For a neater installation, secure the power
cord and the float switch cord to the
discharge pipe with wire ties or hose
clamps. Keep the cords separated from
each other on opposite sides of the pipe.

Completing the Installation

1. After the initial installation, be sure to check the pump operation by filling the sump

with water and observing the pump through one full cycle. The pump should run for
10 seconds after the lower float drops.

Note: When the pump activates, it should have

a “normal pumping” sound. Any abnormal sound, vibration, or lack of output is the
signal of a problem. Stop the pump and refer to the
troubleshooting guide.

2. Replace the pit cover making sure not to pinch or crimp

the pump wire with the cover. The pit cover either has
a ‘hole punch’ that will allow the cord to be passed
through or one can be drilled in the cover.

Product Operation

Dual Float Switch

The dual float switch contains two large floating rings
enclosed within a protective cage. Water will lift the

WARNING

WARNING

NOTICES

PUMP

WIRE

AIR BLEED

HOLE

FLOOR

JOIST

SLOPE

PIPE

DOWN

SURGE

PROTECTOR

DISCHARGE

PIPE

GATE

VALVE

UNION/CHECK

VALVE

PRO SERIES
PUMP

DOUBLE

FLOAT

BRICKS

DRAIN   TILE

FLOAT WIRE

DUAL FLOAT CONTROLLER

PLUGGED INTO

AC OUTLET

PIT COVER

Controller

Dual Float

Consider a Pro Series Battery 
Backup Sump Pump System

Glentronics, Inc.

800.991.0466    www.stopflooding.com

M

o

d

el

N

o.

DFC1

This installation must be in accordance with the National
Electric Code and all applicable local codes and ordinances.

Make sure the outlet is single phase, 115V and 60HZ
for all the pump installations.

2

9C

9D

9F

SURGE

PROTECTOR

DISCHARGE

PIPE

GATE

VALVE

U

DUAL FLOAT CONTROLLER

PLUGGED INTO

AC OUTLET

P

PUMP

WIRE

FLOAT

WIRE

Controller

Dual Float

Consider a Pro Series Battery 

Backup Sump Pump System

Glentronics, Inc.    

800.991.0466

www.stopflooding.com