![Prosense S-DP4 User Manual Download Page 5](http://html.mh-extra.com/html/prosense/s-dp4/s-dp4_user-manual_1618712005.webp)
5
PRS-UM-DP4-EN-Rev.03-05.06.2020
Technical Specifications
Power Source
220VAC ±10% 50/60 Hz
Power Consumption 27VDC/250mA - 6.75W max. (without connected detectors)
Inputs (Internal)
4 Analogue 4-20mA
Relay outputs
FAULT, ALARM1, ALARM2, AUX
Contact ratings
3A, 24VDC or 3A 120VAC
Display
Graphic LCD (128x64)
LED indicators
FAULT, ALARM1, ALARM2, AUX, BATT, POWER for overall status
Power/On, Fault, Alarm LEDs for each detector channel
Backup battery
12V 7A/h (Optional)
Operating Temp.
-10: +60C
0
Humidity
15-95% non condensing
Housing
ABS IP66 (546 X 276 X 186 mm)
Weight
5,75 kg
Main power fuse
2A
Backup battery fuse 2A
Warm-up time
Up to 2 minutes
Delay time
Panel can recognize any special state in 2 minutes
Special States
Fault (Fault Relay de-energised)
Overrange (Alarm Relay(s) energised)
EMC conformity
EN 61326-1 Group-1 Class-A
IEC conformity
IEC 60079-29-1:2106
Program release
V3.02
Special condition
Do NOT install in hazardous area
Table
1: Technical specifications