5. TECHNICAL DATA
5.1 OPERATING CONDITIONS
The lock operation environment must be explosion-safe, free of current-conducting dust or
gases that cause metal corrosion and destroying insulation of current conductors and electric
elements, free of current-carrying dust or water vapor, and preventing ingress of water, steam,
fuel and lubricants.
Climatic operating conditions: У3.1 as per GOST 15150-69 with extended temperature range:
ambient temperature: -30 to +50
°С;
Relative air humidity: not higher than 98 % at 25
°С or lower temperatures without moisture
condensation and hoar-frost formation;
installation indoors or outdoors excluding ingress of moisture, dust, dirt, etc. inside the lock.
5.2 TECHNICAL DATA
Modification
Promix-SM420.10
Promix-SM420.10.1
Design
normally closed
DC supply voltage U, V
12±2
Current consumed, А
0.15 (at 12V)
Availability of sensors
-
door position sensor
Supply pulse width (max), s
not rated
Minimum pause between
pulses, s
not rated
Lock weight (max), kg
0.08
Latch holding force (min), kg
150
6. INSTALLATION AND CONNECTION
6.1 LOCK AND LATCH MOUNTING
1. Install the latch in the area designed for installation.
2. Insert the latch into the lock and fix the lock so that the latch enters it until click.
3. Connect the lock (see cl. 6.2) and function test by applying supply voltage. The lock must
unlock the latch. Open the door so that the latch disengages with the lock.
4. If the latch is not unlocked when power is supplied, push the door in the area of lock fixation
and apply voltage. Then adjust the latch length providing for the necessary free play and
alignment.
6.2 CONNECTING PROCEDURE
The lock operation is controlled by supplying and blocking power. For this purpose a controller
(control board) or a switch (button) is generally used. The controller is mounted in accordance
with its certificate.
Connect the lock power wires adhering to the following polarity: