8.4 Inputs and outputs
Tab. 3: Alarm relay
Terminal
Signal
Description
Function
Protective cir‐
cuit
Perform‐
ance
Load type
XR1
1
C-root
Alarm relay P1 Alarm message
potential-free
Varistor
Max.
690VA
< 3 A
Only ohmic
load
2
N -N/O
2
NC
Tab. 4: Output relay
Terminal
Signal
Function
Protective circuit
Performance Load type
XR2
1
L (switched)
Output relay 230
V, feeding
R-C circuit and
varistor - fuse F4
Max.
1100VA (≤
5A) starting
current, max.
30A for 0.5s
Ohmic and
inductive (up
to cos phi =
0.4)
2
N
3
PE
XR3
1
L (switched)
Output relay 230
V, feeding
R-C circuit and
varistor - fuse F4
Max.
1100VA (≤
5A) starting
current, max.
30A for 0.5s
Ohmic and
inductive (up
to cos phi =
0.4)
2
N
3
PE
XR4
1
L (switched)
Output relay 230
V, feeding
R-C circuit and
varistor - fuse F6
Max.
1100VA (≤
5A) starting
current, max.
30A for 0.5s
Ohmic and
inductive (up
to cos phi =
0.4)
2
N
3
PE
XR5
1
L (switched)
Output relay 230
V, feeding
R-C circuit and
varistor - fuse F6
Max.
1100VA (≤
5A) starting
current, max.
30A for 0.5s
Ohmic and
inductive (up
to cos phi =
0.4)
2
N
3
PE
XR6
1
L (switched)
Output relay 230
V, feeding
R-C circuit and
varistor - fuse F4
Max.
1100VA (≤
5A) starting
current, max.
30A for 0.5s
Ohmic and
inductive (up
to cos phi =
0.4)
2
N
3
PE
XR7
1
L (switched)
Output relay 230
V, feeding
R-C circuit and
varistor - fuse F6
Max.
1100VA (≤
5A) starting
current, max.
30A for 0.5s
Ohmic and
inductive (up
to cos phi =
0.4)
2
N
3
PE
Technical data
33