OPERATING YOUR RG3000-E
Connect your RG3000-E to a 230 V outlet and close both valves on the RG3000-E.
Open the valves to the cylinder and system and make sure no air is in the hoses, only
clean refrigerant. Open the outlet valve on the unit .Switch the main power switch to the
ON position. The fan and compressor will start running. Slowly open the inlet valve on
the unit and the refrigerant will start to move.
OPERATING PROCEDURES
NOTE:
To change from Recovery mode to Purge:
If available, close the valve from the system to the inlet hose and wait untill
the LP gauge shows 0,1 bar. Then close the Inlet valve of the RG3000-E.
Turn the unit off after the unit goes in to vacuum and switch off the RG3000-
E. Close the outlet valve of the RG3000-E and close the valve on the
cylinder.
NORMAL RECOVERY
PURGE / AUTO EVACUATE