10.  Now  generate  a  MAXIMUM  position  control  signal  to  drive  the 
actuator to the fully OPEN position (direct acting mode). Attach a DMM 
to terminals 11 (-), and 12 (+) and set to match the DIP switch setting in 
step 4 (above). Adjust trimmer VR51 to achieve 20.0mA or 10.0vdc. 

11. Generate a MINIMUM position control signal to drive the actuator 
to the fully CLOSED position (direct acting mode).  Adjust trimmer VR2 
fi rst clockwise 3~ 6 turns or 3 ~ 6 turns counterclockwise until the RED 
LED just comes on and stays on.

12.  Now  generate  a  MAXIMUM  position  control  signal  to  drive  the 
actuator to the fully OPEN position (direct acting mode).  Adjust trimmer 
VR1 fi rst counterclockwise 3~ 6 turns or 3 ~ 6 turns clockwise until the 
GREEN LED just comes on and stays on.

Calibration  is  now  complete.  Reattach  mid  position  spacer  ring,  4 
bottom screws and fi nally the top cover.

9. Apply  power  to  the  actuator  and  generate  a  MINIMUM  position 
control signal to drive the actuator to the fully CLOSED position (direct 
acting mode). Attach a DMM to terminals 11 (-), and 12 (+) and set to 
match the DIP switch setting in step 4 (above). Adjust trimmer VR52 
to achieve 4.0mA or 2.0vdc. 

Page 4 of 6  P1.A..P Series 

8. Place hex wrench in the #3 cam set screw, loosen and move cam 
back  clockwise  and  then  counterclockwise  into  the  switch  until  the 
switch “clicks”. Then move 1 degree further into the switch and snug 
up on the set screw. This will assure the aux switch will “trip” before 
the actuator reaches it’s end of travel.

FM1

1

_

P1

A_

P

_

F078P17 V

er C 01051

1