![Promation Engineering P1 A P Series Field Manual Download Page 1](http://html1.mh-extra.com/html/promation-engineering/p1-a-p-series/p1-a-p-series_field-manual_1616247001.webp)
Field Manual
P1.A..P Series
Proportional Control
ISO5211 F07 8P17
The following procedure is to be followed for set-up, calibration, testing and use of the P1 Series Proportional Control
quarter-turn electric actuators. Each unit is shipped from the factory with initial calibration of cams and switches completed.
However, these are general settings and serve as a starting point for proper calibration of the actuator in its’ real-world
application.
Note: The P1.A actuator out put shaft drives CW to close (as viewed from above). However, the indicator shaft
turns CW to open (as viewed from above).
This design utilizes NO MECHANICAL stops.
Determine if any adjustments are required
BEFORE
making any changes to cams or controller settings. Make the power
and control connections per the wiring diagram on page 2. Apply power to the actuator and wait 20 seconds for the
controller to power up.
The proportional control card has been calibrated and tested at the factory to provide full scale response between
0 degrees and 90 degrees operating range. Typically all that is required is a power supply and a control signal to
initialize and put the actuator into service with no need for any adjustments.
Important Note:
THIS ACTUATOR MUST HAVE THE EMT FITTINGS WATER TIGHT WITH CONDUIT DRAINAGE INSTALLED A N D
POWER SUPPLIED TO UNIT TO KEEP THE HEATER WARM AT THE TIME OF INSTALLATION .
l
This unit should NOT be stored outside unless it is powered up.
l
When this unit is NOT powered up, it should be stored in a clean, dry environment at all times.
Conventions used in this manual:
1. All references to rotation are as viewed from ABOVE the actuator.
The default settings in the controller are as follows:
1. Input/Output Signal: 4-20mA (unless otherwise specifi ed at time of Factory order)
2. Signal Response:
Direct Acting (max signal = OPEN)
3. Loss of Signal:
Fail in Position
Page 1 of 6 P1.A..P Series
PROMATION
ENGINEERING
Precision Actuation for Industry
Actuator Specifi cations
Torque lb/Nm
Supply Voltage
Max Inrush Current
Running Current
Runtime (90
O
@60/50Hz)
Weight
Mechanical Connections
Electrical Entry
Electrical Terminations
Environmental Rating
Manual Override
Control
Case material
Motor Protection
120vac or 230vac Operation
Motor Protection
12v/24v AC/DC Operation
Ambient Temperature
Operating Range
7lbs / 3.2kg
ISO5211 F07 8pt 17mm
(2) 1/2” NPT
14 - 18 Ga.
4, 4X
5mm Wrench Drive
Proportional
Aluminum Alloy, Powder Coated
DC Brush Type
275
O
F/135
O
C Thermal H Class
-22
o
F to +150
o
F
-30
o
C to +65
o
C
P1.A...P
445”lbs / 50Nm
0.8A
1.0A
1.5A
0.6A
0.3A
0.5A
24vac/vdc
230vac
120vac
12sec / 13sec
15sec
FM1
1
_
P1
A_
P
_
F078P17 V
er C 01051
1
...Partners, Above and Beyond
3.0A
0.5A
12vac/vdc