REV 7.5.1   /   PL-INSTL-TREECOM-EN

PL-TREE-COM Principles

1.   The Prolon PL-TREE-COM is a wireless communication device that transmits and receives Modbus RS485 data over radio frequency 

 

communication (2.4GHz)

2.   Its goal is to wirelessly extend, complement, or replace standard RS485 wired daisy-chains, where a physical connection would be 

 

impractical or uneconomical. 

(Figure 1)

3.  The TREE-COM modules communicate on dedicated wireless subnet "channels", where a unique "ROOT" module talks with one or 

 

multiple "LEAF" units on the same channel. 

 

3a)  Channel identification is made through dipswitches. Up to 128 different channels may be created.

 

3b) All TREE-COM communicating on a given channel must be set to the same dispswitch channel number. 

 

3c)  These dipswitches are not to be mistaken with the controllers' Modbus address, they are for channel identification only.

  

(Figure 2)

 

3d) The "ROOT" module is always connected to a Modbus "Master" device, the "LEAF" always connect to "follower" devices. 

Figure 2

PL-M2000-RTU

Modbus: 20

PL-TREE-COM

Channel: 1

ROOT

PL-TREE-COM

Channel: 1

LEAF

PL-VC2000

Modbus: 21

PL-VC2000

Modbus: 22

PL-TREE-COM

Channel: 1

LEAF

Figure 1

4.  Each wireless segment must have one TREE-COM set as a "ROOT".
 

4a)  The "ROOT"/"LEAF" function is activated using dipswitch number #8.

 (Figure 2)

 

4b) There can only be one "ROOT" on any given segment.

 

4c)  The "ROOT" can have as many "LEAF" modules as needed by the Prolon system.

 

4d) The PL-TREE-COM, set as a "ROOT", communicates with all its "LEAF" modules

Summary of Contents for PL-TREE-COM

Page 1: ...INSTALLING THE TREE COM with Prolon REV 7 5 1 PL INSTL TREECOM EN www proloncontrols com 1 877 977 6566 info proloncontrols com 17510 Rue Charles Suite 100 Mirabel QC J7J 1X9...

Page 2: ...ster Controller with multiple Follower Controllers fully wireless network 9 Master Controller with multiple Follower Controllers wired wireless hybrid network 10 Master Controller with multiple Follow...

Page 3: ...All TREE COM communicating on a given channel must be set to the same dispswitch channel number 3c These dipswitches are not to be mistaken with the controllers Modbus address they are for channel ide...

Page 4: ...quality read at the LEAF module must be at least 30 to achieve proper communication Figure 5 NOTE Aligning TREE COM modules face to face is highly recommended for distances beyond 200 ft A signal qual...

Page 5: ...a LEAF 8d SND RED This LED indicates if data is being transmitted on the RS485 bus Blinking occurs in quick short bursts 8e REC GREEN This LED indicates if data is being received from the RS485 bus Bl...

Page 6: ...caracteristics 10a When a PL NC2000 is present it must have firmware version 7 5 0 or later to support TREE COM communication 10b Any Digital wall sensor T200 T500 T1000 connected to a TREE COM must...

Page 7: ...NOT be connected using a PL TREE COM M2000 only 1 The PL TREE COM connected to the communicating wall sensor must be set as the ROOT 2 The PL TREE COM connected to the Single Zone Unit Controller must...

Page 8: ...0 using a PL TREE COM Figure 9 1 The PL TREE COM connected to the communicating wall sensor NEEDS to be set as the ROOT INT port 2 The PL TREE COM connected to the VAV controller must be set as the LE...

Page 9: ...ork Follower Controllers VC2000 C1050 VAV T1100 FLX BLR etc can be connected wirelessly to a Master Unit Controller such as a PL M2000 HP or RTU or a PL C1050 RTU or HP 1 Each controller must have its...

Page 10: ...to gap the link between the Master and all its Followers Figure 11 1 The PL TREE COM on the M2000 Master s side must be connected in the NET port and be set as the ROOT 2 The Followers Network PL TREE...

Page 11: ...spliced and re united using TREE COM modules regardless of their location within a Prolon network Figure 12 1 The TREE COM that is hardwired to the Modbus Master PL M2000 RTU must be set in ROOT mode...

Page 12: ...the PL NC2000 via the RS 485 OUT port must be set as the ROOT 2 The PL TREE COM connected to individual PL M2000 or PL C1050 via the INT communication port must be set as the LEAF 3 All PL TREE COM mo...

Page 13: ...it has established a connection with its ROOT module 3 Measuring a ROOT module using NFC will not yield signal quality but rather number of associated LEAF modules it is able to communicate with 4 To...

Page 14: ...ed up PL TREE COM device 1 To access NFC tap on the vertical ellopsis icon at the top right of the screen 2 Tap on Settings 3 Approach and hold the back of the mobile device very near the powered up T...

Page 15: ...connecting 1 To scan the TREE COM tap on the settings icon in the left bottom corner 2 Tap on Scan PL TREE COM 3 When ready to detect approach and hold the back of the mobile device very near the powe...

Page 16: ...30 to 60 is considered low quality To communicate succesfully with signals in this range it is best to increase the number of retries in Focus PC to 10 or 20 attempts so to reduce the likelyhood of fa...

Page 17: ...eans or translated to another language without prior written consent of Prolon All specifications are nominal and may change as design improvements are introduced Prolon shall not be liable for damage...

Reviews: