Prolon Control Systems
Lonbox PSW5000
Users Manual
Page 4
The following table documents the different configuration modes that a digital input can be used in.
SWA_ACTIVE_ON
Used for toggle switch types
When input is active the configured on level is transmitted.
When input is passive OFF = 0% 0 is transmitted
SWA_ACTIVE_OFF
Used for toggle switch types
When input is active OFF = 0% 0 is transmitted.
When input is passive, the configured on level is transmitted.
SWA_ON_LEVEL
When activated the configured on level is transmitted.
SWA_ON_LAST
When activated, the last known on level is transmitted.
SWA_OFF
When activated, OFF 0% 0 is transmitted
SWA_AUTO
When activated an invalid switch value is transmitted 127.5% -1,
this is used to reset manual override of a light controller.
SWA_DIM_UP
When pressed and as long as the switch is held active the
switch level is dimmed up using configured step value.
SWA_DIM_DOWN
When pressed and as long as the switch is held active the
switch level is dimmed down using configured step value.
SWA_DIM_UP_ON_LEVEL
If clicked configured on level is transmitted.
If held active the switch level is dimmed up using configured
step value.
SWA_DIM_UP_ON_LAST
If clicked the last known on level is transmitted.
If held active the switch level is dimmed up using configured
step value.
SWA_DIM_DOWN_OFF
If clicked, OFF 0% 0 is transmitted
If held active the switch level is dimmed down using configured
step value.
SWA_DIM_UP_DOWN_OFF_ON_LEVEL
If clicked either OFF 0% 0 or configured on level is transmitted.
If held active the switch level is dimmed up or down using
configured step value.
SWA_DIM_UP_DOWN_OFF_ON_LAST
If clicked either OFF 0% 0 or last known on level is transmitted.
If held active the switch level is dimmed up or down using
configured step value.
SWA_TOGGLE
Toggles the switch level transmitted between off and configured
on level.
SWA_SETTING_ON
When activated sends SET_ON with a setting level as
configured in on level and a rotation of 0 (zero)
SWA_SETTING_OFF
When activated sends SET_OFF with a setting level as