6. Operation
Power On/Off
Once the inverter has been properly installed, press the power switch to turn on the unit. The
unit will work automatically in line mode or inverter mode according to input utility power's
status. When press the power switch again, the unit will be turned off.
LED Indicators & Audible Alarms
There are three indicators (Green/Red/Yellow) in the front panel of the unit.
Status
Indicator
Alarm
Line mode
Green LED lighting
Off
Battery mode
Yellow LED lighting
Off
Shutdown mode
Yellow LED flashing every 5 sec.
Off
Battery charging at
power on.
Green LED flashing every 2 sec.
Off
Battery fully charged at
power on.
Green LED lighting
Off
Battery charging at
power off.
Green LED flashing every 4 sec.
Off
Battery fully charged at
power off.
Green LED flashing every 10 sec. Off
Battery weak at battery
mode.
Yellow LED flashing every sec.
Sounding every 2 sec.
Fault mode.
Red LED lighting
Continuously sounding for
30 min. and then
shutdown.
The unit is overload.
Red LED flashing for 0.5 sec.
every sec.
Sounding every 0.5 sec.
The unit is over charged.
Red LED flashing every 4 sec.
Continuously sounding for
30 min. and then
shutdown.
Operation Mode Selector
a). “UPS”: setting for conventional electrical appliance.
If you select this mode, the unit's input utility range will be 162~290VAC as normal home UPS.
If the utility is higher or lower than this range, the unit will transfer to inverter mode
automatically. And you can connect the computer systems or other precision home
equipment when you select this operation mode.
b). “INV.”: setting for energy saving
If you select this mode, the unit's input utility range will be extended to 90~280VAC. If the
utility is higher or lower than this range, the unit will transfer to inverter mode automatically.
So, you can connect the home equipments, such as light bulb, fluorescent tube, fan, or TV
on this mode.
Caution!!
If you select the “INV.” mode and connect the computer to the output of the unit,
the computer may reboot if the input voltage is too low to be accepted.
7. Trouble Shooting
Use the table below to solve minor problems.
Problem
Possible Cause
Solutions
Utility power is
normal but the unit
is in battery mode.
AC input power cord is not
connected well.
Check AC input power connection.
Input breaker is activated.
Reset the input breaker.
When power fails,
the backup time is
shorten.
The unit is overload.
Remove some non-critical loads.
Battery voltage is too low.
Charge the unit at least 8 hours.
Battery capacity is not full
even after charge the unit for
at least 8 hours.
Check the date code of the battery. If
the batteries are too old, replace the
batteries.
No LED display on
the front panel when
the utility power is
normal.
The unit is not turned on.
Press power switch to turn on the
unit.
Battery is not connected well. Check the external battery cable and
terminal. Make sure all the battery
connections to the unit are all correct.
Battery defect.
Replace the batteries.
Battery voltage is too low.
Charge the unit at least 8 hours.
The unit is in fault
and restart circularly.
The unit is overload.
Verify that the load matches the
capability
specified
in
the
specification.
Output is short circuited.
Check the loads and remove loads
which cause short circuit.
If there is any abnormal situations occur, which doesn't list above, please call the service
people immediately for professional examine.