Profort multiGuard DIN6 Quick Manual Download Page 4

 
 

SET-UP - MANAGEMENT  

 

 

 

   

.

 

Version 1.2  

Pg. 

4

 

Add text in HIGH 
interval 

1234 V1 B HIGH TEMP 

Alarm text in HIGH interval (higher than 30 
degrees C.)

 

Activate output on 
alarm  

1234 G1

 

(G1 = 10 secs., G2 = 20 secs., G3 = 30 secs., G4 = 
1 min, G5 = 2 mins, G6 = 4 mins, G7 = 8 mins, G8 
= 16 mins og G9 = constant.) 

Sets the relay output to activate in case of alarm on 
an input. Output is determined by zone. 

Output follows 
state on input  

1234 GA

 

Indicates that the output follows the corresponding 
input if text is added. 

Notice: input signal has higher priority than  
command S0 (S + zero) and B0 (B + zero) 

Deactivate output 
in case of alarm 

1234 G0 

Output is not activated in case of alarm (G+null) 

Add macro 0 for 
return of 
temperature 

1234 M0 TEMP <V1 R> 

The unit returns value on analogue 1 (e.g. 
temperature) when a text message with the word 
‘TEXT’ is sent (‘1234’ omitted in macros). If 
using the Profort app, the macro names are shown 
as buttons in the app. 

 
 

 

Additional help: see the manual on www.profort.com

 

Control with call from telephone 

Call the unit. Press 1234 (password) when the connection has been established and await two ’beeps’. Enter 
the desired code and hang up. 

Examples of codes: 

 

*0x (as zero + zero)    

Pulses output x for 10 secs. 

 

*1x(as 1 + zero) 

 

Breaks output x  

*2x (as 2 + zero) 

 

Closes output x 

 

 

Performs macro x 

 

If # is pressed while receiving voice message, the subsequent persons in the call list will not 

 

receive an alarm. 

Summary of Contents for multiGuard DIN6

Page 1: ...le 230V 12 24V AC DC and if necessary a rechargeable 9V battery 3 Turn on the power A red diode is lit After approx 20 sec the diode flashes approx every 2 sec and the unit is ready The GSM unit inter...

Page 2: ...com Set up via masterView 1 Open a browser on your PC tablet or smartphone 2 Type http setup masterview dk in the address bar and choose setup or login via www profort dk Log on to the portal or crea...

Page 3: ...total N2 N9 NA 10 NB 11 NP 25 Delete 1234 N1 Deletes receiver in space no 1 Text on input Add 1234 A0 BREAK TEXT TEXT on input 0 by open break A0 A3 1234 L0 END TEXT TEXT on input 0 by close make L0...

Page 4: ...4 G0 Output is not activated in case of alarm G null Add macro 0 for return of temperature 1234 M0 TEMP V1 R The unit returns value on analogue 1 e g temperature when a text message with the word TEXT...

Page 5: ...loads information about GSM transmission power and battery level Example OK OK SQ xx xx transmission power in percentage 25 is least acceptable value 1234 V1 R Downloads measurements on analogue input...

Page 6: ...ble to set up 20 macros Set up macro with command 1234 M1 NAME COMMAND Sets up macro 1 M0 M9 and R0 R9 under the name NAME and adds command in More commands in the same macro can be separated by semic...

Page 7: ...RS485 D D gnd Inputs digital Max 1V 2 mA GND Min 18V max 30 V 24V DC Input analog 0 10V DC 0 4 20mA PT 100 Profort temperature sensor Profort no 007995 Pulse and minute counter Max 10Hz 6 numbers Inpu...

Page 8: ...24V power supply 9V rechargeable back up battery acquisition Modbus interface IP 65 box Touch display for set up and programming multiGuard Remote IO 1 relay output 2 senders of infrared codes for hea...

Reviews: