background image

 

 

QUICK GUIDE for 6 modules 

 

 
 

 

www.profort.com  

Pg. 

1

 

Installation  

1.

 

Prepare a SIM card so that the PIN code is 1234 or is deactivated. Mount the card in the unit. The 
unit has now 1234 as password or runs without a password. The card must be placed as shown 
below. 

2.

 

Connect inputs, outputs and power cable (230V/12-24V AC/DC) and if necessary a rechargeable 9V 
battery.  

3.

 

Turn on the power. A red diode is lit. After approx. 20 sec. the diode  flashes approx. every 2 sec., 
and the unit is ready. 

 

The GSM unit interior 

 
  

DIP-switch for analog input 

 

 

1 ON: 

 0-10 VDC 

2 ON: 

 0/4-20 mA 

3 ON: 

 PT-100 

4 ON: 

 Profort probes 

All OFF:  

 digital input 

Voltage 

  

Output:  

AC max. 230 VAC, 6A 

 

DC max. 30 VDC, 6A 

Input, digital: 

max. 24 VDC 

 

max. power 2 mA 

Input, analog: 

max. 0-10 VDC 

 

Only print voltage when   

         The DIP-switch 1 is on, and 2-4  
         are off 

Summary of Contents for multiGuard DIN6

Page 1: ...le 230V 12 24V AC DC and if necessary a rechargeable 9V battery 3 Turn on the power A red diode is lit After approx 20 sec the diode flashes approx every 2 sec and the unit is ready The GSM unit inter...

Page 2: ...com Set up via masterView 1 Open a browser on your PC tablet or smartphone 2 Type http setup masterview dk in the address bar and choose setup or login via www profort dk Log on to the portal or crea...

Page 3: ...total N2 N9 NA 10 NB 11 NP 25 Delete 1234 N1 Deletes receiver in space no 1 Text on input Add 1234 A0 BREAK TEXT TEXT on input 0 by open break A0 A3 1234 L0 END TEXT TEXT on input 0 by close make L0...

Page 4: ...4 G0 Output is not activated in case of alarm G null Add macro 0 for return of temperature 1234 M0 TEMP V1 R The unit returns value on analogue 1 e g temperature when a text message with the word TEXT...

Page 5: ...loads information about GSM transmission power and battery level Example OK OK SQ xx xx transmission power in percentage 25 is least acceptable value 1234 V1 R Downloads measurements on analogue input...

Page 6: ...ble to set up 20 macros Set up macro with command 1234 M1 NAME COMMAND Sets up macro 1 M0 M9 and R0 R9 under the name NAME and adds command in More commands in the same macro can be separated by semic...

Page 7: ...RS485 D D gnd Inputs digital Max 1V 2 mA GND Min 18V max 30 V 24V DC Input analog 0 10V DC 0 4 20mA PT 100 Profort temperature sensor Profort no 007995 Pulse and minute counter Max 10Hz 6 numbers Inpu...

Page 8: ...24V power supply 9V rechargeable back up battery acquisition Modbus interface IP 65 box Touch display for set up and programming multiGuard Remote IO 1 relay output 2 senders of infrared codes for hea...