3. EARTHING MODULE 

For the right earthing and the optimal functioning of the module, connect itself to the earth through copper 
cables having at least a 16 mm

2

 cross-section. 

To avoid possible side effects, the earth references of the connection and power supply cable of the 
indicator and of the connected instrument must be at the same potential. 
 

GENERAL NOTES: 

-

 

Use Earth plate of suitable length, in order to obtain a total resistance of earthing plant lower 
than 1 Ω.  

-

 

One should check and remove, if necessary, the connection between the earth and the neutral 

wire of the electrical installation.   

 