Indicator light functions 

 

A. Indicator 

light 

-  The indicator light is illuminated for one second when the power is connected. 

-  The indicator light illuminates when the transmitter sends data to Modbus (M models only). 

Selecting measuring range 

Measuring range can be selected with the jumper S1. 

 

A. 

Measuring range selection jumper 

Pa 0…500

 

0…1000 *

)

 

S1 

 

 

*

)

  Factory setting. The 0…1000 Pa range is also used for the custom range setting. 

 

The custom range is 0…1000 Pa as a default. The range can be changed by using ML-SER tool or by defining the 
high limit to the Modbus register 40006 (the low limit is 0 Pa). 

Summary of Contents for Sensortec PEL 1000-M

Page 1: ...n open surrounding space pressure Accordingly the duct under pressure is detected by connecting the measuring point to connector and by leaving the connection open Install the measuring hoses carefull...

Page 2: ...cond when the power is connected The indicator light illuminates when the transmitter sends data to Modbus M models only Selecting measuring range Measuring range can be selected with the jumper S1 A...

Page 3: ...e after one hour of powering the transmitter 1 Unplug the plastic tubes from the inlets 2 Press the zeroing button until the indicator light lights up without flashing A Indicator light B Zeroing butt...

Page 4: ...ER tool You can proceed in the menu by pressing the M and OK buttons The values can be changed with the and buttons The value is accepted with the OK button The following menu structure contains the f...

Page 5: ...source calibration pressure must be at least 275 Pa Hoses for pressure connections Calibration 1 Connect the transmitter and the reference pressure meter to the same pressure source 2 Connect the ML S...

Page 6: ...lected pressure range Custom range menu The CUSTOM RANGE menu is for setting the custom pressure range limits The custom range is in use when all the pressure range selection jumpers are placed Output...

Page 7: ...Modbus can be terminated by placing the Modbus termination jumper S7 A Modbus termination jumper Supported Modbus functions 0x01 Read Coils 0x02 Read Discrete Inputs 0x03 Read Holding Registers 0x04 R...

Page 8: ...200 200 200 200 Pa 30004 Analogue output voltage unsigned 0 1000 0 10 00 V The custom range is 0 1000 Pa as a default The range can be changed by using ML SER tool or by defining the high limit to the...