background image

USER GUIDE

KRM-1 & KRM-2

 

7 (8) 

 

Produal Oy 

Keltakalliontie 18, 48770 Kotka FINLAND 

Tel: +358-10-219 9100 / Fax: +358-5-230 9210 

[email protected] 

www.produal.com

 

Information is subject to change without prior notice. 

Behaviour of the alarm relay and fault relay and displays, plus reset options 

Valid with 
software 0020 

Smoke alarm 

Device failure / missing detector 

Alarm relay, 
connectors 
11/12/13 

Drops out

 

Drops out 

Alarm relay, 
connectors 
14/15 

Drops out 

Drops out 

LED  
Alarm / Reset 

Lights up 

Lights up 

LED failure 

Does not light up 

Lights up 

Alarm reset or 
failure reset 

With power interruption, alarm button or 

with terminal 9 / 10 provided that sensing 

chamber is free. 

With power interruption, alarm button or with 

terminal 9/10 provided that sensing chamber is free 

+ disturbance has ceased. 

 

MAINTENANCE AND REPAIR 

In order to ensure good performance over a longer period of time the smoke alarms must be tested at least once a 
year. Without maintenance, and depending on environmental conditions, the sensor will become dirty sooner or later, 
and after a certain time will trigger an alarm, which is a false alarm.  

 

NOTE:

 All types will give a specific maintenance requirement signal at a contamination level of 70 % (display flashes, 

relay contamination drops out). There is a contact available for this “contamination” signal (terminals 16/17), and it 
should be connected to the automation station. From a 70 % contamination level or higher the smoke sensor must be 
changed.  

Maintenance and repair procedure 

If, due to operational specifications short term shutdowns cannot be tolerated, measures must be taken to prevent this; 
if necessary by placing a bridge over the alarm contact, but remembering to remove it after completion of the service 
work. After maintenance work, a complete functionality test must be carried out. If defects have appeared they must 
be removed immediately. 

 

Before opening the housing, turn off all supply voltages – The housing may only be opened by a qualified 
electrician. Supply and switching voltages must be observed. 

 

 

1. 

The smoke detector is accessible by removing the cover. 
 

 

 

2. 

By turning the white detector on the base by about 20° to anticlockwise the sensor can be unscrewed. If it is too 
dirty (indicator >70 %), and no later than the prescribed standard of exchange cycles, the sensor must be 
removed and exchanged for a new sensor. 

3. 

If necessary, clean the cover, measuring tube and the inner housing. 

4. 

Check the electrical connections, possibly tightening the terminals. Make visual inspection and clean the 
electrical circuit board if necessary, as well as the inner housing. Check all seals. 

5. 

Assemble all parts. 

Summary of Contents for KRM-1

Page 1: ...eed Depending on the cross section of the ventilation duct the air collecting tube may be cut to a length of 160 mm This minimum length of 160 mm must not be undercut This way up to 100 mm ø can be monitored in conjunction with the FP KRM fitting plate In the ideal case install the KRM when structurally possible where flow meters etc are normally attached so there is a laminar airflow along the me...

Page 2: ... in air duct direction Air duct forking Air duct narrowing air duct enlargement Air duct device Mounting procedure 1 Drill a hole Ø 43 44 mm in diameter at the intended mounting location NOTE Installation of the measuring tube is possible either from the top bottom or side of the channel for all duct cross sections for round ducts as well 2 Determine how long the measuring tube must be If necessar...

Page 3: ...and insert it into opening in the air duct Install the fitting plate B Insert the assembled adapter plate A into the measuring tube by sliding the measur ing tube through the grommet and screw the adapter plate onto the fitting plate B using the 4 self tapping screws Install the sensor with fitting plate into air duct Then the insulation D can be installed B D C A 6 When installing sensor outdoors...

Page 4: ...ination red Test Reset 3 4 Power supply 24 Vac dc 1 2 5 6 7 8 Bus B Bus B Bus A Bus A RS485 for information MOD BAC models KRM 1 KRM 2 KRM 2 MOD KRM 2 BAC NOTES The cable jacket for field wire connecting must be done as near as possible to the terminal block For wires longer than 10 mm the wire must be fixed by a cable clip near the terminal block or insulated in pairs with a suitably protective t...

Page 5: ... D G H J D J 3 For testing the smoke sensor the housing must not be opened It has a self closing test opening J in the centre of the transparent cover Use test gas spray Insert the test spray s tube fully into the test opening appx 1 5 mm deep and release as much test gas as needed until the smoke sensor activates Please do not spray too much otherwise the smoke sensor may display a higher degree ...

Page 6: ...t button or closing the bridge circuit between terminal 9 10 00 99 flashing BUS address Display only with MOD BAC versions after pressing the address buttons T3 and T4 directly on the circuit board LEDs Meaning Explanation Alarm reset red Smoke alarm or failure Reset after failure Briefly press alarm reset button KRM immediately restarts Reset after alarm Press and hold the alarm reset button for ...

Page 7: ...lay flashes relay contamination drops out There is a contact available for this contamination signal terminals 16 17 and it should be connected to the automation station From a 70 contamination level or higher the smoke sensor must be changed Maintenance and repair procedure If due to operational specifications short term shutdowns cannot be tolerated measures must be taken to prevent this if nece...

Page 8: ... 7 Check with the operator about the function of the downstream systems and components such as Turning off of fans Closing of flaps Notification to the building automation system When checking network failure and recovery does the sensor return to its normal function and does it unlock again from the state smoke alarm and return to its normal function when there is no longer any present Release is...

Reviews: