Current Setpoint
Signed 16
5,0 … 37,0 (C)
13
DAY EXTENSION period
Signed 16
1 … 480 (min)
FUNCTION CODE 05 - WRITE SINGLE COIL
1
Overdrive mode (Cooling and Heating outputs)
Bit0
On - Off
2
NIGHT- mode
Bit1
On - Off
3
SERVICE ALARM
Bit2
On - Off
5
Fan Speed 1 asked
Bit4
On - Off
6
Fan Speed 2 asked
Bit5
On - Off
7
Fan Speed 3 asked
Bit6
On - Off
8
Fan Speed 4 (Auto) asked
Bit7
On - Off
FUNCTION CODE 06 - WRITE SINGLE REGISTER
2
Coils 16-01
16 bit
3
Set Fan Speed
Signed 16
0 - 1 - 2 - 3 - 4
4
Cooling Output (Overdrive mode = “on” )
Signed 16
0,0 … 100,0 (%)
5
Heating Output (Overdrive mode = “on” )
Signed 16
0,0 … 100,0 (%)
6
Set Point by Network ( DAY value only )
Signed 16
5,0 … 37,0 (C)
13
DAY EXTENSION period
Signed 16
1 … 480 (min)
FUNCTION CODE 16 - WRITE MULTIPLE REGISTERS
2
Coils 16-01
16 bit
3
Set Fan Speed
Signed 16
0 - 1 - 2 - 3 - 4
4
Cooling Output (Overdrive mode = “on” )
Signed 16
0,0 … 100,0 (%)
5
Heating Output (Overdrive mode = “on” )
Signed 16
0,0 … 100,0 (%)
6
Set Point by Network ( DAY value only )
Signed 16
5,0 … 37,0 (C)
FUNCTION CODE 22 - MASK WRITE REGISTER
2
Coils 16 - 01
16 bit
AND 0 … 0xFFFF
OR 0 … 0xFFFF