HLS34 Modbus FCU/VAV Controllers installation instructions 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Model Type  

Model 

Description 

 

HLS34 

HLS34 Room Temperature Controller with Modbus Networking Capability  

 

 

 

 

 

 

Technical Data 

Power Supply 

24Vac/dc (20…26V), <1VA 
NOTE! If using DC-voltage only 0..10V outputs are operational 

 

 

 

 

Inputs 

Built-in Temperature Sensor  
1 x NTC10 e.g. TEHY -NTC10 (for control or measurement only) 
1 x Volt-Free (PIR – normally closed) 
1 x Analogue (CO2 measurement) 

 

 

 

 

Outputs 

2 x 0..10Vdc (Heating/Cooling Actuators, VAV or Fan Speed Control) 
4 x 24Vac Triacs, 1A maximum (3-Point Actuators / Thermic Actuators) 

 

 

 

 

Communications 

RS-485 Modbus RTU, 9600/19200/38400 bps, 8 data bits, Parity None, 1 Stop Bit (Up to 
128 devices per segment) 

 

 

 

 

Set Point Adjustment 

DAY SETPOINT 
21°C 

±

3°C (factory default); setpoint adjustable pressing “+” and “-“ buttons within 

programmable 

±

 range; network setpoint available via Modbus or in the configuration mode 

NIGHT SETPOINT 
5-20°C (factory default 18°C); adjustment available via Modbus or in configuration mode 

 

 

 

 

Accuracy 

±

0.5°C 

 

 

 

 

Dead Zone 

DAY mode       Dz = 0..3°C (factory default = 0.3°C) 
Relaxed mode Dz = 0..10°C 

 

 

 

 

Proportional Band 

Xp = 1..8°C (factory default = 4°C) 

 

 

 

 

Integral Action Time 

Tn = 50..500s (factory default = 300 sec) 

 

 

 

 

3-Point Control  
Actuator Runtime 

Mt = 30..300s (factory default = 180 sec) 

 

 

 

 

Protection Class 

IP20 

 

 

 

 

Operating Humidity 

0..95% rH non-condensing 

 

 

 

 

Wiring Terminals 

1.5 mm

2

 

 

 

 

 

Housing 

ABS Plastics 

 

 

 

 

Dimensions 

87W x 86H x 32D mm 

 

 

 

The HLS34 is specifically designed for individual room temperature 
and zone control applications. The controllers have built-in RS-485
channel for Modbus communication. The controllers can be 
connected to any supervisory software/system that supports 
Modbus RTU.  
 
The HLS34 has built-in display and unique touch sensitive buttons 
for adjusting the user parameters and to configure the controller.  
 
The controller supports 0..10V actuators, 3-point controlled 
actuators and thermic actuators. One of the controller 0..10Vdc 
outputs can be configured for fan speed control via FCRY3 relay 
module. 
 
Temperature is detected by the internal sensor of the HLS34. If an 
external temperature sensor such as return air sensor or remote 
room sensor is required, this can be connected to the wiring 
terminals provided on the controller. The external sensor type is 
NTC10.  
 
The controller has DAY and NIGHT operating modes. When in the 
NIGHT mode the controller can be overridden to the DAY mode via 
a hardware input, by touching day extension button or over the 
MODBUS network. The controller has also a CO2 measurement 
input for boosting the ventilation (fan speed) in case of high CO2 
level in the room space. 

Summary of Contents for HLS34

Page 1: ...egral Action Time Tn 50 500s factory default 300 sec 3 Point Control Actuator Runtime Mt 30 300s factory default 180 sec Protection Class IP20 Operating Humidity 0 95 rH non condensing Wiring Terminals 1 5 mm2 Housing ABS Plastics Dimensions 87W x 86H x 32D mm The HLS34 is specifically designed for individual room temperature and zone control applications The controllers have built in RS 485 chann...

Page 2: ...oducts meet the requirements of directive 89 336 EEC and standards EN50081 1 1992 Emission and EN50082 2 1995 Immunity Wiring Terminals The electrical installation device connection and commissioning can only be carried out by qualified professionals and according to the local wiring regulations AIR SIDE APPLICATION WIRING ...

Page 3: ...ol The controller has adjustable dead zone between heating and cooling modes The controller DAY setpoint SP is calc ulated as follows SP SPnetwork SPlocal where SPnetwork is setpoint set via Modbus network and SPlocal is the setpoint set by the user by pressing and buttons SPlocal range is limited at the commissioning stage default 3 C In the NIGHT mode the controller controls to the NIGHT FROST s...

Page 4: ...CO2 transmitter is connected to the controller analogue input U1 the controller can be enabled to boost the fan speed switch the fan On in case of high CO2 content in the occupancy space This is a very useful feature to provide demand based ventilation High CO2 level overrides the fan speed set by the temperature based fan speed control Day Extension via digital input The controller has hardware d...

Page 5: ...ol The HLS34 handheld tool allows quick configuration of large number of controllers To configure the controller locally first remove the top cover A CONFIGURATION MODE JUMPER is located below the LCD display When the jumper is set the controller is in normal operation By removing the jumper the controller enters to the configuration mode Once the configuration has been completed by setting the ju...

Page 6: ...1 1 1992 Emission and EN50082 2 1995 Immunity Network Diagram Up to 128 HLS34 controllers can be connected to a single network segment The diagram below illustrated the typical installation where the room controllers are connected on the floor level to the Netbiter embedded web server Each Netbiter holds a time schedule for the floor to switch the controller between day and night operation modes ...

Page 7: ...y Occupied NIGHT mode to DAY mode Bit1 On Off 3 DAY EXTENSION NIGHT mode to DAY mode Bit2 On Off 4 EXT S External Sensor Bit3 On Off 5 Fan Speed 1 run Bit4 On Off 6 Fan Speed 2 run Bit5 On Off 7 Fan Speed 3 run Bit6 On Off FUNCTION CODE 03 READ HOLDING REGISTERS 2 Coils 16 01 16 bit 3 Fan Speed Set by Network Signed 16 0 1 2 3 4 4 Cooling Output Set by Network Signed 16 0 0 100 0 5 Heating Output ...

Page 8: ... Off 7 Fan Speed 3 asked Bit6 On Off 8 Fan Speed 4 Auto asked Bit7 On Off FUNCTION CODE 06 WRITE SINGLE REGISTER 2 Coils 16 01 16 bit 3 Set Fan Speed Signed 16 0 1 2 3 4 4 Cooling Output Overdrive mode on Signed 16 0 0 100 0 5 Heating Output Overdrive mode on Signed 16 0 0 100 0 6 Set Point by Network DAY value only Signed 16 5 0 37 0 C 13 DAY EXTENSION period Signed 16 1 480 min FUNCTION CODE 16 ...