ML-SER TOOL 

With the ML-SER tool you can change the device settings, controller and wireless network settings for example. 

Connecting ML-SER tool to the device 

1. 

Remove the display / HD-AL3 option. 

2. 

Connect the ML-SER cable to the connector. 

 

A. ML-SER cable 

CO

2

 measurement value shows on the ML-SER tool display. 

Summary of Contents for HDHFL

Page 1: ...sitions inside the network Wiring Device wiring and commissioning can only be carried out by qualified professionals Always make the wirings while the power is switched off NOTE CO2 measurement causes...

Page 2: ...n 1 2 poor 3 5 satisfactory 6 9 good 10 Go to the FLTA base station and check that the signal strengths are adequate 11 Set the FLSER tool switch to the OFF position The transmitter starts to communic...

Page 3: ...on is subject to change without prior notice ML SER TOOL With the ML SER tool you can change the device settings controller and wireless network settings for example Connecting ML SER tool to the devi...

Page 4: ...m CO2 proportional band 100 10000 C set point 18 26 C C proportional band 1 0 32 0 RH set point 0 100 RH proportional band 10 100 Yellow indicator light illumination point 400 10000 ppm Red indicator...

Page 5: ...ssioning tool When the wireless settings are made with one tool the other tool cannot be used to change or check the wireless settings Calibration menu M OK CALIBRATION OK OK OK Modbus ID 0 Offset CO2...

Page 6: ...FF Cont CO2 Cont OK OK OK OK Modbus ID PI Controlmode 300 Integr time s 700 CO2 Setpoint OK 500 CO2 Propor band P Controlmode OK TEMPERATURE Cont OK OK OK OK Modbus ID PI Control mode 300 Integr time...

Page 7: ...55 AL3 menu M OK OK OK AL3 750 YELLOW 1250 RED Yellow indicator light illumination point 400 10000 ppm Red indicator light illumination point 400 10000 ppm AL3 menu is available if HD AL3 option is i...

Page 8: ...c method is not in use the device should be calibrated every 6 12 months The recommended calibration interval is 5 years even if the ABCLogic is in use ABCLOGIC TM self calibration feature ABCLogic Au...