COMMISSIONING
Selecting the transmitter position
The device can be installed in dry surroundings (IP20) by screws on the wall surface or on the standard flush mounting
box. The recommended installation height is 150…180 cm.
The device position should be selected carefully. All the error factors that can affect to the measurements should be
eliminated as well as possible. The following list defines the typical measurement error factors.
direct sun light
occupant
proximity
air flow coming from windows or doors
air flow coming from ventilation nozzles
air flow coming from the flush mounting box
differential temperature caused by external wall
NOTE:
The wireless network coverage affects also on the transmitter positioning. With the help of FLSER
commissioning tool, you can see the wireless network coverage and select the ideal transmitter positions inside the
network.
Wiring
Device wiring and commissioning can only be carried out by qualified professionals. Always make the
wirings while the power is switched off.
NOTE:
CO
2
measurement causes a current peak to the supply voltage. This can produce an error to the analogue
outputs when using long and thin cables. It is recommended to increase the wire cross section area in long cable
situations (e.g. by using free pairs) to ensure reliable measurement signal.
Connecting to wireless network
IMPORTANT:
The device wireless network settings are made by using either FLSER or ML-SER
commissioning tool. When the wireless settings are made with one tool, the other tool cannot be used to
change or check the wireless settings.
Connecting to wireless network by using FLSER tool
1.
Disconnect the transmitter power supply.
2.
Set the FLSER tool switch to the MID position.
3.
Push the + and - buttons to select the FLTA base station master ID (MID) to which you are connecting the
transmitter.
4.
Set the FLSER tool switch to the S-RID position.
5.
Push the + and - buttons to select the sensor ID (SID) for the transmitter.
6.
Push the OK button.
“Wait” message starts to flash on the FLSER tool display. You have now approximately 30 seconds to complete
the next step.
6
MID=
8
SID=