COMMISSIONING 

Selecting the transmitter position 

The device can be installed in dry surroundings (IP20) by screws on the wall surface or on the standard flush mounting 
box. The recommended installation height is 150…180 cm. 

The device position should be selected carefully. All the error factors that can affect to the measurements should be 
eliminated as well as possible. The following list defines the typical measurement error factors. 

 

direct sun light 

 occupant 

proximity 

 

air flow coming from windows or doors 

 

air flow coming from ventilation nozzles 

 

air flow coming from the flush mounting box 

 

differential temperature caused by external wall 

NOTE:

 The wireless network coverage affects also on the transmitter positioning. With the help of FLSER 

commissioning tool, you can see the wireless network coverage and select the ideal transmitter positions inside the 
network. 

Wiring 

Device wiring and commissioning can only be carried out by qualified professionals. Always make the 
wirings while the power is switched off. 

 

 

NOTE:

 CO

2

 measurement causes a current peak to the supply voltage. This can produce an error to the analogue 

outputs when using long and thin cables. It is recommended to increase the wire cross section area in long cable 
situations (e.g. by using free pairs) to ensure reliable measurement signal. 

Connecting to wireless network 

IMPORTANT: 

The device wireless network settings are made by using either FLSER or ML-SER 

commissioning tool. When the wireless settings are made with one tool, the other tool cannot be used to 
change or check the wireless settings. 

Connecting to wireless network by using FLSER tool 

1. 

Disconnect the transmitter power supply. 

2. 

Set the FLSER tool switch to the MID position. 

3. 

Push the + and - buttons to select the FLTA base station master ID (MID) to which you are connecting the 
transmitter. 

 

4. 

Set the FLSER tool switch to the S-RID position. 

5. 

Push the + and - buttons to select the sensor ID (SID) for the transmitter. 

 

6. 

Push the OK button. 

“Wait” message starts to flash on the FLSER tool display. You have now approximately 30 seconds to complete 
the next step. 

MID= 

SID= 

Summary of Contents for HDHFL

Page 1: ...sitions inside the network Wiring Device wiring and commissioning can only be carried out by qualified professionals Always make the wirings while the power is switched off NOTE CO2 measurement causes...

Page 2: ...n 1 2 poor 3 5 satisfactory 6 9 good 10 Go to the FLTA base station and check that the signal strengths are adequate 11 Set the FLSER tool switch to the OFF position The transmitter starts to communic...

Page 3: ...on is subject to change without prior notice ML SER TOOL With the ML SER tool you can change the device settings controller and wireless network settings for example Connecting ML SER tool to the devi...

Page 4: ...m CO2 proportional band 100 10000 C set point 18 26 C C proportional band 1 0 32 0 RH set point 0 100 RH proportional band 10 100 Yellow indicator light illumination point 400 10000 ppm Red indicator...

Page 5: ...ssioning tool When the wireless settings are made with one tool the other tool cannot be used to change or check the wireless settings Calibration menu M OK CALIBRATION OK OK OK Modbus ID 0 Offset CO2...

Page 6: ...FF Cont CO2 Cont OK OK OK OK Modbus ID PI Controlmode 300 Integr time s 700 CO2 Setpoint OK 500 CO2 Propor band P Controlmode OK TEMPERATURE Cont OK OK OK OK Modbus ID PI Control mode 300 Integr time...

Page 7: ...55 AL3 menu M OK OK OK AL3 750 YELLOW 1250 RED Yellow indicator light illumination point 400 10000 ppm Red indicator light illumination point 400 10000 ppm AL3 menu is available if HD AL3 option is i...

Page 8: ...c method is not in use the device should be calibrated every 6 12 months The recommended calibration interval is 5 years even if the ABCLogic is in use ABCLOGIC TM self calibration feature ABCLogic Au...