![Procon MelcoRETAIL MINI Instruction Manual Download Page 36](http://html1.mh-extra.com/html/procon/melcoretail-mini/melcoretail-mini_instruction-manual_1608981036.webp)
Page 31
9.3. Initialisation
When the MelcoRETAIL MINI powers up it will set the mode, which will be determined by the room temperature.
If less than the Heating Setpoint the unit will be set to HEAT mode with a setpoint of 28ºC.
If greater than or equal to the Cooling Setpoint the unit will be set to COOL mode with a setpoint of 19ºC.
If between the Heating and Cooling Setpoints the unit will be set to FAN mode.
All manuals and user guides at all-guides.com
all-guides.com