Procom SL250TYLA-D Owner'S Operation And Installation Manual Download Page 5

   5

       

WARNING:   Rework   worksheet,  adding   the  space  of   the  adjoining  unconfined  space.  The

combined  spaces  must   have  enough  fresh air  to supply  all  appliances  in  both  spaces.

If  the actual  Btu/Hr  used  is  less  than  the  maximum  Btu/Hr  the  space  can  support, the  space  is  an
unconfined  space. You  will  need  no  additional  fresh  air  ventilation.

3. Add  the  Btu/Hr of all fuel burning appliances in the space.

     Vent-free heater                                                      Btu/Hr
     Gas water heater*                                                   Btu/Hr
     Gas furnace                                                            Btu/Hr
     Vented gas heater                                                   Btu/Hr
     Gas heater logs                                                       Btu/Hr
     Other gas appliances* +                                          Btu/Hr
     Total                                =                                       Btu/Hr

    *Do  not  include  direct-vent  gas  appliances. Direct-vent  draws  combustion  air  from  the  outdoors  and
       vents to the outdoors.

4. Compare  the  maximum  Btu/Hr  the  space  can  support  with  the  actual amount of Btu/Hr used.
                         Btu/Hr (maximum the space can support)
                          Btu/Hr (actual amount of Btu/Hr used)
         Example :  51,200 Btu/Hr(maximum the space can support)
                           56,000 Btu/Hr(actual amount of Btu/Hr used)
The  space  in  the  above  example  is  a  confined  space  because  the  actual  Btu/Hr  used  is  more  than  the
maximum  Btu/Hr  the  space  can  support.
You  must  provide  additional  fresh  air.  Your  options  are  as  follows:
A.  Rework  worksheet, adding  the  space  of  an  adjoining  room. If  the  extra  space  provides  an  unconfined
space, remove  door  to  adjoining  room  or  add  ventilation  grills   between  rooms. See  Ventilation  Air  From
Inside  Building
 (below).
B.  Vent  room  directly  to  the  outdoors. See  Ventilation  Air  From  Outdoors (below) .
C.  Install  a  lower  Btu/Hr  heater, if  lower  Btu/Hr  size  makes  room  unconfined.

Figure  2 -Ventilation  Air  from  Inside  Building

 Example:
Gas  water  heater          30,000        Btu/Hr
Vent-free  heater    +      26,000        Btu/Hr
  Total                          =   56,000       Btu/Hr

        

 WARNING:  If  the  area  in  which  the  heater  may  be  operated  is  smaller  than  that  defined  as

an  unconfined space or  if  the building  is  of  unusually  tight  construction, provide  adequate
combustion  and  ventilation air by  one of   the  methods  described  in  the  National Fuel  Gas  Code,

ANS  Z223.1, Section  5.3  or  applicable  local  codes.

This  fresh air  would come  from an adjoining  un-
confined space.  When  ventilating  to  an  adjoining
unconfined space, you  must  provide  two  perma-
nent  openings: one within 12" of  the  ceiling  and
one  within 12" of  the  floor on  the  wall  connecting
the  two  spaces (see  options 1 and  2, Figure 2).
You  can  also  remove  door  into adjoining  room
(see  option 3, Figure 2). Follow  the  National  Fuel
Gas  Code. NFPA  24/ANS  Z223.1.  Section 5.3,  Air
for  Combustion  and  Ventilation  for required size of
ventilation grills or ducts.

Ventilation  Air  From  lnside  Building

Ventilation  Air  From Outdoors

Provide extra fresh air by using ventilation grills or
ducts. You must provide two permanent openings:
one within 12" of the ceiling and one within 12" of
the floor. Connect these items directly to the out-
doors or spaces open to the outdoors. These spaces
include attics and crawl spaces. Follow the National
Fuel Gas Code, NFPA 54/ANS Z223.1, Section 5.3.
Air for Combustion and Ventilation for required size
of ventilation grills or ducts.
IMPORTANT:Do not provide openings for  inlet
or outlet air into attic if attic has a thermostat-
controlled power vent. Heated air entering the
attic will activate the power vent.

Figure  3 -Ventilation  Air  from  Outdoors

Summary of Contents for SL250TYLA-D

Page 1: ...ENTED ROOM HEATERS Water vaporis a by product of gas combustion An unvented room heater productes approximately one 1 ounce 30ml of water for every 1 000 BTU s 3KW s of gas input per hour Refer to pag...

Page 2: ...e Propane LP supply tank s indoors 3 If you smell gas Shut off gas supply Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call yo...

Page 3: ...ee operation State and local codes in some areas prohibit the use of vent free heaters UNPACKING 1 Remove top inner pack 2 Tilt carton so that fireplace is upright 3 Remove protective side packaging 4...

Page 4: ...ing if You Have a Confined or Unconfined Space Use this worksheet to determine if you have a confined or unconfined space Space Includes the room in which you will install heater plus any adjoining ro...

Page 5: ...oom unconfined Figure 2 Ventilation Air from Inside Building Example Gas water heater 30 000 Btu Hr Vent free heater 26 000 Btu Hr Total 56 000 Btu Hr WARNING If the area in which the heater may be op...

Page 6: ...late If your gas supply can not meet that requirement do not install heater Call dealer where you bought heater from for proper heater type Figure 4 Minimum Clearance to Wall CLEARANCES TO COMBUSTIBLE...

Page 7: ...gas is commonly known as wellhead gas CAUTION Only use a new black iron or steel pipe Internally tinned cop per tubing may be used in certain areas Check your local codes Use pipe of 1 2 diameter or g...

Page 8: ...ure of liquid soap and water to gas joints Bubbles forming show a leak 5 Correct all leaks immediately 6 Reconnect heater and equipment shutoff valve to gas supply Check reconnected fittings for leaks...

Page 9: ...chnician to inspect the appliance and to replace any part of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS 1 STOP Read the safety informatuion above 2 Set the...

Page 10: ...55 F 12 78 C If no heat is desired turn the gas cntrol knob to the PILOT position Main Burner Operation Description of Gas Control Knob OFF position PILOT position LO HI will allow the hydraulic ther...

Page 11: ...pas sageways of heater clean Inspect these areas of heater before each use Have heater inspected yearly by a qualified service person Heater may need more frequent cleaning due to excessive lint from...

Page 12: ...Pilot flame not touching thermocouple This allows thermocouple to cool causing the pilot flame to go out This problem could be caused by one or both of the following A Low gas pressure B Dirty or part...

Page 13: ...n logs or inside of fireplace 1 Improper log placement 2 Air holes at burner inlet are blocked 3 Burner flame holes are blocked 1 Properly locate logs see Installing Logs page 9 2 Clean out air holes...

Page 14: ...o return the defective part to the factory Warranty card PARTS NOT UNDER WARRANTY Contact authorized dealers of this prod uct or Parts Central If they can t supply original replacement part s call PRO...

Page 15: ...ngle iron Figure 3 Insert the pinhole on the upper part of log 4 into the pin on the left side of log 1 Place the lower part on the flat roof at the left side of log 3 Figure 4 Insert the pinhole on t...

Page 16: ...16 ILLUSTRATED PARTS BREAKDOWN SN250TYLA D SL250TYLA D...

Page 17: ...0 4 2 0 L E G N r o t c e j n I 1 8 0 1 0 5 2 0 L E P L r o t c e j n I 1 9 0 0 0 0 7 3 B E y l b m e s s A e b u T t e l t u O 1 1 0 1 3 1 F 1 8 V R N G N 3 I F 1 8 V R r o t a l u g e R 1 1 1 8 1 F...

Page 18: ...18 ILLUSTRATED PARTS BREAKDOWN SN250TYLA D SL250TYLA D 20...

Page 19: ...1 0 0 L S n m u l o C t h g i R 1 1 8 1 0 1 1 0 L E e r i W g n i t a r o c e D r e p p U 1 1 9 4 0 3 0 2 0 0 L S r e v u o L d i M r e p p U 2 2 0 1 6 0 6 0 0 L E r o t c e l f e R e d i S 2 2 1 1 1...

Page 20: ...thread that previously bond the electrical wire to collect and pack the outside connection wire of the cable 6 Place operation control housing at the bottom of stove Use two black screws provided in b...

Page 21: ...21 INSTALLING BLOWER ACCESSORY BLOWER ACCESSORY MODEL NFHTX186 Figure 4 A Routing Power Cord Figure 4 B Routing Power Cord Wiring Diagram Decal Figure 5 Mounting Control Housing SIDE VIEW...

Reviews: