Problem

Possible Cause

Corrective Action

Heater produces a whis-

tling noise when burner 

is lit.

1. Turning control knob to high 

(5) position when burner is 

cold.

2. Air in gas line.

3. Air passageways on heater 

are blocked.

4. Dirty  or  partially  clogged 

burner orifice.

1. Turn control knob to low (1) 

position and let warm up for 

a minute.

2. Operate  burner  until  air  is 

removed from line. Have gas 

line  checked  by  local  gas 

supplier.

3  Observe  minimum  installa-

tion  clearances  (Figure  4, 

page 9)

4  Clean burner (see 

Care and 

Maintenance

,  page  21)  or 

replace burner orifice.

Heater produces a click-

ing/ticking noise just after 

burner is lit or shut off.

1. Metal  is  expanding  while 

heating or contracting while 

cooling.

1. This  is  common  with  most 

heaters.  If  noise  is  exces-

sive,  contact  qualified  ser-

vice technician.

White  powder  residue 

forming  within  burner 

box or on adjacent walls 

or furniture

1. When  heated,  the  vapors 

from  furniture  polish,  wax, 

carpet  cleaners,  etc.,  turn 

into white powder residue.

1. Turn heater off when using 

furniture polish, wax, carpet 

cleaner or similar products.

Heater  shuts  off  in  use 

(ODS operates).

1. Not enough fresh air is avail-

able.

2. Low line pressure.

3. ODS/pilot  is  partially 

clogged.

1. Open window and/or door for 

ventilation.

2. Contact local gas supplier.

3. Clean  ODS/pilot  (see 

Care 

and Maintenance

, page 21).

Gas  odor  exists  even 

when control knob is in 

OFF position.

1. Gas  leak.  See 

Warning 

Statement

 at top of page 23.

2. Control valve is defective.

1. Locate and correct all leaks 

(see 

Checking Gas Connec-

tions

, page 16).

2. Contact customer service.

Moisture/condensation 

noticed on windows.

1. Not  enough  combustion/

ventilation air.

1. Refer  to 

Air for Combus-

tion and Ventilation

 require-

ments, page 7.

TROUBLESHOOTING

Summary of Contents for PFS PCS100T

Page 1: ...ry or loss of life Do not store or use gasoline or other flammable va pors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do n...

Page 2: ...Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manual for correct installation and operational procedures For assistance or additi...

Page 3: ...oxide poisoning may lead to death CARBON MONOXIDE POISONING Early signs of carbon monoxide poisoning resemble the flu with headaches dizziness or nausea If you have these signs the heater may not be w...

Page 4: ...If heater shuts off do not relight until you have provided fresh outside air If heater keeps shutting off have it serviced 6 Do not run heater Where flammable liquids or vapors are used or stored Und...

Page 5: ...ater is equipped to operate on either propane or Natural gas The heater is shipped from the factory ready for connecting to propane The heater can easily be changed to Natural gas by having your quali...

Page 6: ...low humidity atmosphere experienced during cold weather The following steps will help ensure that water vapor does not become a problem 1 Be sure the heater is sized properly for the application incl...

Page 7: ...enting of vented fuel burning appliances WARNING This heater shall not be installed in a room or space unless the required vol ume of indoor combustion air is provided by the method de scribed in the...

Page 8: ...nto adjoining room see option 3 Figure 2 Follow the National Fuel Gas Code ANSI Z223 1 NFPA 54 Air for Combustion and Ventilation for required size of ventilation grills or ducts Ventilation Air From...

Page 9: ...as to baccosmoke aromaticcandles cleaning fluids oil or kerosene lamps etc in the air exist may cause walls to discolor Figure 4 Minimum Clearances to Wall and Ceiling IMPORTANT Vent free heaters add...

Page 10: ...UNGER The regulator will not work and the warranty will be voided Theinletregulatoriscolorcoded for identification of the correct gastype Blueisforpropane LP gas andyellowisfornaturalgas INSTALLATION...

Page 11: ...FOR NATURAL GAS INSTALLATION YELLOW 1 Remove the metal cap installed over the NG regulator inlet Metal Cap Metal Cap DO NOT REMOVE Yellow Natural Gas Plunger Install Gas Fitting Here 2 Install metal c...

Page 12: ...he clearances shown in Figure 7 NOTICE Surface temperatures ofadjacentwallsandmantelsbe comehotduringoperation Walls and mantels above the fireplace may become hot to the touch If installed properly t...

Page 13: ...x Combustible materials should never overlap the firebox front facing Figure 10 Rough Opening for Corner Installation Figure 11 Installing Fireplace Insert Into Mantel CABINET MANTEL If using a cabine...

Page 14: ...cessible location The equip ment shutoff valve is for turning on or shutting off the gas to the appliance For propane installations apply pipe joint sealant lightly to male threads This will prevent e...

Page 15: ...cation and Gas Line Access into Stove Cabinet External Regulator with Vent Pointing Down Propane Supply Tank Equipment Shutoff Valve Ground Joint Union 3 8 NPT Pipe Nipple Tee Joint Reducer Bushing to...

Page 16: ...ll damage heater regulator 2 Cap off open end of gas pipe where equip ment shutoff valve was connected 3 Pressurize supply piping system by either opening propane supply tank valve for propane gas or...

Page 17: ...age 18 Check all other internal joints for leaks 7 Turn off heater see To Turn Off Gas Ap pliance page 19 WARNING Failure to posi tion the parts in accordance with these diagrams or failure to use onl...

Page 18: ...nly your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it call a qualified service technician Force or attempted repair...

Page 19: ...ervice technician or gas supplier for repairs Until repairs are made light pilot with match If control knob does not pop up when released contact a qualified service technician or gas supplier for rep...

Page 20: ...and LOW 1 Note The thermostat sensing bulb measures the temperature depending on housing con struction TO TURN OFF GAS TO APPLIANCE MANUAL LIGHTING PROCEDURE INSPECTING BURNERS IMPORTANT Owner s shoul...

Page 21: ...for any blockage and clean as necessary Blocked air holes will create soot NG 3 3 5 WC Natural Gas Shown LP 8 11 WC NG 3 3 5 WC Natural Gas Shown LP 8 11 WC CARE AND MAINTENANCE WARNING Turn off heate...

Page 22: ...Remove any large particles of dust dirt lint or pet hair with a soft cloth or vacuum cleaner nozzle 5 Blow air into the primary air holes on the injector holder 6 In case any large clumps of dust hav...

Page 23: ...peration of the unit on the wrong gas propane If your natural gas supply exceeds 9 5 WC the unit will not operate Either contact your gas supplier to check and adjust the inlet pressure or a qualified...

Page 24: ...e 2 Turn control knob to PILOT position 3 Fully press in control knob while pressing ignitor button 4 Continue holding down con trol knob Repeat igniting op eration until air is removed 5 Clean ODS pi...

Page 25: ...gh air 2 Inlet gas pressure is too low 3 Gas regulator is damaged 1 Check burner for dirt and debris If found clean burner see Care and Maintenance page 21 2 Contact local gas supplier 3 Replace gas t...

Page 26: ...is exces sive contact qualified ser vice technician White powder residue forming within burner box or on adjacent walls or furniture 1 When heated the vapors from furniture polish wax carpet cleaners...

Page 27: ...674 When calling please have your model and serial numbers of your heater ready REPLACEMENT PARTS Note Use only original replacement parts This will protect your warranty coverage for parts replaced u...

Page 28: ...www usaprocom com 200159 01B 28 PARTS MODEL PCS100T PCS150T 3 4 1 2...

Page 29: ...replacement parts follow the instructions listed under Replacement Parts on page 27 of this manual ITEM PART DESCRIPTION QTY 1 150PCS102B 02 Screen Assembly 1 2 15T1500B 01 Gas Train Assembly 1 3 PIMD...

Page 30: ..._____________________ ________________________________________________________________ ________________________________________________________________ ________________________________________________...

Page 31: ..._____________________ ________________________________________________________________ ________________________________________________________________ ________________________________________________...

Page 32: ...rt s MUST be obtained through ProCom Heating Inc who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty IMPORTANT The heater MUST be...

Reviews: