INSTALLATION

Figure 13 - Equipment Shutoff Valve

CHECKING GAS CONNECTIONS

Open

Closed

Equipment 

Shutoff Valve

PRESSURE TESTING HEATER GAS 

CONNECTIONS

1.  Open equipment shutoff valve (see Fig-

ure 13).

2.  Open main gas valve located on or near 

gas meter for natural gas or open propane 

supply tank valve.

3.  Make sure control knob of heater is in the 

OFF position.

4.  Check  all  joints  from  equipment  shutoff 

valve to control valve (see Figure 14 or 15). 

Apply a noncorrosive leak detection fluid 

to all joints. Bubbles forming show a leak.

5.  Correct all leaks at once.

6.  Light heater (see 

Lighting Instructions

 on 

page 19). Check all other internal joints 

for leaks.

7.  Turn off heater (see 

To Turn Off Gas Ap-

pliance

, page 20).

Control Valve 

Location

Control Valve 

Location

Equipment 

Shutoff Valve

Equipment Shutoff Valve

External Regulator

Propane 

Supply Tank

Figure 14 - Checking Gas Joints for 

Propane Gas

Figure 15 - Checking Gas Joints for 

Natural Gas

Gas Meter

 WARNING: Test all gas piping 

and connections, internal and 

external to unit, for leaks after 

installing or servicing. Correct 

all leaks at once.

 WARNING: Never use an open 

flame to check for a leak. Apply a 

noncorrosive leak detection fluid 

to all joints. If bubbles form, there 

is a leak. Correct all leaks at once.

PRESSURE TESTING GAS SUPPLY 

PIPING SYSTEM

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.  Disconnect heater with its appliance main 

gas valve (control valve) and equipment 

shutoff valve from gas supply piping sys-

tem. Pressures in excess of 1/2 PSIG will 

damage heater regulator.

2.  Cap off open end of gas pipe where equip-

ment shutoff valve was connected.

3.  Pressurize supply piping system by either 

opening  propane  supply  tank  valve  for 

propane gas or opening main gas valve 

located on or near gas meter for natural 

gas or using compressed air.

4.  Check all joints of gas supply piping sys-

tem. Apply  noncorrosive  leak  detection 

fluid  to  all  joints.  If  bubbles  form,  there 

may be a leak.

5.  Correct all leaks at once.

6.  Reconnect heater and equipment shutoff 

valve to gas supply. Check reconnected 

fittings for leaks.

Test Pressures Equal To or Less Than 

1/2 PSIG (3.5 kPa)

1. 

Close equipment shutoff valve (see Figure 13).

2.  Pressurize supply piping system by either 

opening  propane  supply  tank  valve  for 

propane gas or opening main gas valve 

located on or near gas meter for natural 

gas or using compressed air.

3.  Check all joints from gas meter to equip-

ment shutoff valve for natural gas or pro-

pane  supply  to  equipment  shutoff  valve 

for propane (see Figure 14 or 15). Apply 

a noncorrosive leak detection fluid to all 

joints. Bubbles forming show a leak.

4.  Correct all leaks at once.

Summary of Contents for FBNSD400T-ZC Series

Page 1: ...mmediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be perform...

Page 2: ...of this manual WARNING Improper installation adjustment al teration service or maintenance can cause injury or property damage Refer to this manual for correct in stallation and operational procedures...

Page 3: ...low fans to blow directly into the heater Avoidanydraftsthatalterburner flame pattern including ceiling fans Altered burner patterns can cause sooting SAFETY WARNING Do not attempt to access or change...

Page 4: ...oducts may create a white powder residue within burner box or on adjacent walls or furniture 8 Always run heater with control knob at PILOT IGN or ON 1 thru 5 positions never set control knob between...

Page 5: ...h air PIEZO IGNITION SYSTEM This heater is equipped with an electronic piezo control system This system requires AAA batteries provided THERMOSTAT HEAT CONTROL The control automatically cycles the bur...

Page 6: ...alth of Mas sachusetts Sellers of unvented propane or natural gas fired supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upon sale of the unit In the State of Massachuset...

Page 7: ...erfresh air for this and other fuel burning appliances in your home Today s homes are built more energy efficient than ever New materials increased insulation and new construction methods help reduce...

Page 8: ...nto adjoining room see option 3 Figure 2 Follow the National Fuel Gas Code ANSI Z223 1 NFPA 54 Air for Combustion and Ventilation for required size of ventilation grills or ducts Ventilation Air From...

Page 9: ...or ash clean out doors located on floor or wall of fire place If not drafting may cause pilot outage or sooting Use a heat resistant sealant Do not seal chimney flue damper WARNING Never install the h...

Page 10: ...ill be pushed back by the fitting making all of the adjustments for the gas being supplied DO NOT REMOVE THE PLUNGER The regulator will not work and the warranty will be voided Theinletregulatoriscolo...

Page 11: ...eshelf3 8 NPTpipe cap This will damage the plung ers located inside the regulator DO NOT TRY TO REMOVE THE PLUNGERS FROM INSIDE THE REGULATOR THE PLUNGER WILLBEPUSHEDBACKASTHE FITTINGISINSTALLED REMOV...

Page 12: ...should not be less than 12 see Figure5 B Clearance from the top of the fireplace to the ceiling must not be less than 48 BUILT IN FIREPLACE INSTALLATION WARNING Do not allow any combustiblematerialsto...

Page 13: ...standoff brackets in the hardware bag Remove screws from the top of the firebox Install brackets with screws as shown in Figure 10 3 Carefully set fireplace in front of rough opening with back of fir...

Page 14: ...p is an acceptable al ternative to test gauge connection Purchase the optional CSA design certified equipment shutoff valve from your dealer WARNING A qualified ser vice technician must connect heater...

Page 15: ...f you do not reduce incom Figure 12 External Regulator with Vent Pointing Down External Regulator with Vent Pointing Down Propane Supply Tank Equipment Shutoff Valve Ground Joint Union 3 8 NPT Pipe Ni...

Page 16: ...Ifbubblesform there isaleak Correctallleaksatonce PRESSURE TESTING GAS SUPPLY PIPING SYSTEM Test Pressures In Excess Of 1 2 PSIG 3 5 kPa 1 Disconnect heater with its appliance main gas valve control v...

Page 17: ...s very important to install the logs exactly as instructed Do not modify logs Use only logs supplied with heater Each log is marked with a number This number will help you to identify the logs when in...

Page 18: ...ct For long periods of non operation remove batteries from all components for safety Unscrew ignitor cap and install a AAA battery with the pointing out Replace cap Figure 20 Installing Battery in Ign...

Page 19: ...n under water FOR YOUR SAFETY READ BEFORE LIGHTING LIGHTING INSTRUCTIONS WARNING You must oper ate this heater with the screen in place Make sure screen is installed before running heater NOTICE Durin...

Page 20: ...starting again 10 Make sure heater screen is in place before operating heater 11 If heater will not operate follow the in structions To Turn Off Gas To Appliance and call your service technical or ga...

Page 21: ...ping follow instructions at bottom of this page Notice Do not mistake orange flames with yellow tipping Dirt or other fine particles enter the heater and burn causing brief patches of orange flame App...

Page 22: ...irt lint or pet hair with a soft cloth or vacuum cleaner nozzle 5 Blow air into the primary air holes on the injector holder 6 In case any large clumps of dust have now been pushed into the burner Rep...

Page 23: ...air through the air inlet hole You may blow through a drinking straw if compressed air is not available CABINET ODS PILOT Air Passageways Use a vacuum cleaner or pressurized air to clean Exterior Use...

Page 24: ...pressure switch See instructions below The entire gas delivery piping including con nections inside the heater should be leak tested by the qualified installer After leak testing the qualified instal...

Page 25: ...rn control knob to PILOT position 3 Fully press in control knob while pressing ignitor button 4 Continue holding down control knob Repeat igniting operation until air is removed 5 Clean ODS pilot see...

Page 26: ...oo low 3 Gas regulator is defective 1 Check burner for dirt and debris If found clean burner see Care and Maintenance page 22 2 Contact local gas supplier 3 Replace gas train Slight smoke or odor duri...

Page 27: ...noise is exces sive contact qualified ser vice technician White powder residue forming within burner box or on adjacent walls or furniture 1 When heated the vapors from furniture polish wax carpet cle...

Page 28: ...www usaprocom com 200348 01C 28 PARTS MODEL FBNSD400T ZC 7 8 1 5 2 3 6...

Page 29: ...page 30 of this manual ITEM PART DESCRIPTION QTY 1 161818 01HT Hood 1 2 161368 01HT Left Door Assembly 1 3 161369 01HT Right Door Assembly 1 5 161822 01 Gas Train Assembly 1 6 161338 01 Ignitor 1 7 1...

Page 30: ...c at 1 866 573 0674 for information EQUIPMENT SHUTOFF VALVE For all models Equipment shutoff valve with 1 2 NPT tap Model and serial number of your heater How heater was malfunctioning Type of gas use...

Page 31: ...ified heat propane gas supply might be low propane units only You may feel your gas pressure is too low If so contact your local gas supplier TECHNICAL SERVICE You may have further questions about ins...

Page 32: ...rt s MUST be obtained through ProCom Heating Inc who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty IMPORTANT The heater MUST be...

Reviews: