-8-

Thermocouple

Step 11:

 Press and hold the “

SET

” key for one sec-

ond. The display will read “

HoLd

”. Wait for the display

to reset. After it resets, the display should indicate the
approximate temperature value for the connected pre-
cision resistors (i.e. 511ºF or 266ºC).

Step 12:

 Turn OFF power to the controller and re-

move the precision resistors. Retain for future use.
Reinstall the RTD sensor and rear cover of controller.
Return the calibrated control to service.

The DE20 can be equipped with an optional thermo-
couple sensor board (Item Number 5417).  Installa-
tion requires configuration for the specific thermo-
couple used.  The two wire thermocouple is polar-
ized, therefore it is necessary to connect the negative
lead wire of the thermocouple to the #1 terminal, and
the positive lead to the #2 terminal to maintain proper
polarity.

Equipment needed:

A precise, NIST traceable, thermocouple calibrator
with suitable extension leads to match the thermo-
couple type used.

WARNING!

Calibration procedures require the removal of the
rear cover of the control. It also requires that power
is ON, exposing the technician to potentially lethal
voltages. Exercise EXTREME CARE and wear tested
electrician’s gloves whenever power is on.

Calibration procedure for a thermocouple:

Step 1:

Turn 

OFF

 all power.

Step 2:

Remove rear cover.

Step 3:

Remove T/C sensor.

Step 4:

Install the thermocouple calibrator to termi-

nal #1 and #2

Step 5:

CAREFULLY restore power to the controller,

making sure that you do not come in contact with any
exposed voltage.

Step 6:

Press the decrease “

È

” key and increase

Ç

” buttons simultaneously and hold for approximately

6 seconds.  The display will indicate “AC.0”.  While
the “0” is flashing, use the increase key to change
this to “22”.  Press the “SET” key.  The control display
will read “

CAL1

”.

Step 7:

Adjust the thermocouple calibrator to 0.0ºC

(32.0ºF).

Step 8:

Press and hold the “

SET

” key for one sec-

ond. The display will read “

HoLd

”. Wait for the display

to change to “

CAL2

”.

Step 9:

Adjust the thermocouple calibrator to 250.0ºC

(482.0ºF).

Step 10:

 Press and hold the “

SET

” key for one sec-

ond. The display will read “

HoLd

”. Wait for the display

to reset and display 250.0ºC (482.0ºF).

Step 11:

 Turn OFF power to the control and remove the

thermocouple calibrator. Reinstall the thermocouple
sensor and the rear cover of the control. Return the
control to service.

Voltage Signal Calibration

The DE20 control measures DC voltage and com-
pares that measurement with a “standard” set of val-
ues in the control memory. To restore, update or
merely verify that this “standard” set of values is cor-
rect, do the following:

THERMOCOUPLE

NEGATIVE (-)

POSITIVE (+)

-7-

Optional Item Number 5415 board needed.

The configuration and calibration procedures used
for measuring pure resistance are the same as are
used to configure and calibrate a two wire RTD sen-
sor. However, in the setting configuration mode, the

U1

” sensor type parameter must be set to “

12

”. See

the “

U1

” instructions on page 11. The unit will then

measure pure resistance from 0-1000 ohms.

Note: For a 1000 ohm sensor, the DIP switches
should be OFF, OFF, OFF.  For 100 ohm, check that
the DIP switches are ON, OFF, OFF (see page 13).

RTD devices are precise resistors whose resistance
value varies with temperature.  The DE20 control mea-
sures the RTD resistance and compares that mea-
surement with a “standard” set of values stored in the
control memory.  To restore, update or verify that this
“standard” set of values is correct, do the following:

Equipment needed:

1.

Two precision resistors (tol/- 0.1%
or better) with a fixed value equal to the
nominal value of the RTD (i.e. 1000 ohms or
100 ohms).

2.

A suitable jumper cable to facilitate
changing input resistance.

3.

A short piece of jumper wire (simulates third
wire).

WARNING!

Calibration procedures require the removal of the
rear cover of the control. It also requires that power
is ON, exposing the technician to potentially lethal
voltages. Exercise EXTREME CARE and wear tested
electrician’s gloves whenever power is on.

Calibration procedure for the 3 Wire RTD:

Step 1:

Turn 

OFF

 all power.

Step 2:

Remove rear cover.

Step 3:

Remove RTD sensor.

Step 4:

Install the short piece of jumper wire from ter-

minal #1 to #3.

Step 5:

Install the precision resistors in place of the

RTD sensor, as shown in terminals #2 and #3.

Resistance Signal

3 Wire RTD Sensor

Step 6:

 Install the jumper cable between the loose

end of one of the resistors and the fixed end of the
other resistor to establish an input value of a single
resistor (i.e. 1000 ohms or 100 ohms), as shown.

Step 7:

Carefully restore power to the controller, en-

suring that you do not come in contact with any ex-
posed voltage.

Step 8:

Press the decrease “

È

” key and increase “

Ç

buttons simultaneously and hold for approximately 6
seconds.  The display will indicate “AC.0”.  While the
“0” is flashing, use the increase key to change this to
“22”.  Press the “SET” key.  The display will read 

“CAL1

”.

Step 9:

Press and hold the “

SET

” key for one sec-

ond. The display will read “

HoLd

”. Wait for the display

to change to “

CAL2

”.

Step 10:

 Proceed with CAUTION to avoid SHOCK

hazard. Remove and relocate one end of the jumper
cable to the loose end of the second precision resis-
tor for the second resistance value (i.e. 2000 ohms or
200 ohms), as shown.

M-33-01-02  02/17/11

M-33-01-02  02/17/11

U

U

U

U

U

!

U

U

U

U

U

!

Summary of Contents for DE20

Page 1: ...stance Signal Calibration 7 3 Wire RTD Calibration 7 Thermocouple Calibration 8 Voltage Signal Calibration 8 Current Input Calibration 9 Frequency Signal Calibration 10 Configuration Setup 10 Main Men...

Page 2: ...0 to 1000 F 40 to 538 C F or C field selectable Set Point Range Selectable throughout the input range De energize control output No sensor short protection with Thermocouple sensor Accuracy 0 25 span...

Page 3: ...Using the wiring dia gram supplied with the controller install the required input and output wires Use National Electric Code and local codes for determining wire sizing insula tion terminations etc 3...

Page 4: ...Sensor Number represents degrees Celsius or Fahrenheit as determined by the F5 setting Voltage Sensor Number represents tenths of a volt 0 1 VDC Current Sensor Number represents hundredths of milliam...

Page 5: ...higher than the set point setting on the control During the alarm condition the control relay will de energize the set point relay and flash AAA on the display After enabling this feature you may vie...

Page 6: ...ugh the list of settings to those needing modification 10 Configuration To adjust a setting while in the Configuration Mode use the increase decrease buttons to bring the particular setting into the v...

Page 7: ...trician s gloves whenever power is on Calibration procedure for voltage signal Step 1 Turn OFF all power Step 2 Remove rear cover Step 3 Remove sensor Step 4 Install the voltage calibrator to terminal...

Page 8: ...standard set of values is cor rect do the following THERMOCOUPLE NEGATIVE POSITIVE 7 Optional Item Number 5415 board needed The configuration and calibration procedures used for measuring pure resista...

Reviews: